Plan Review Notes For Permit 07080515 |
Permit Number |
07080515 |
|
Review Stop |
Z |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-03-04 11:12:06 | ***FAILED - REVISION - CHANGING LOCATION OF OUTDOOR | | KITCHEN AND A/C EQUIPMENT*** | | | | | | 1)AS THE NEWLY SUBMITTED FLOOR PLAN/ELECTRIC PLAN | | (SHEET A2/A7) SHOW THE A/C MECHANICAL EQUIPMENT IN A | | DIFFERENT LOCATION FROM WHAT WAS ORIGINALLY APPROVED, | | INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT | | TO ALL PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF | | THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | THAN 4 FEET INTO A REQUIRED SETBACK. | | | | NOTE:NO STRUCTURE/EQUIPMENT SHALL BE BUILT WITHIN THE | | 20 FOOT DRAINAGE EASEMENT . | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | SENT TO "M" - TG |
|