 BUILDING PLAN REVIEW
 PERMIT: 07080505
 ADD: 580 VILLAGE BLVD
 CONT: G.A. RAY INC.
 TEL: (561)714-3740
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE NEW RECEPTIONIST AREA SHALL MEET THE
 REQUIREMENTS OF SECTION 11-7. A PORTION OF THE MAIN
 COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES. SHOW COMPLIANCE.
  
 3)FBC. 803.1 INTERIOR WALL AND CEILING FINISHES SHALL
 BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84. THE NEW
 WALL AND CEILING SHALL HAVE A FLAME SPREAD OF CLASS A /
 B OR C.
  
 4)SHOW THE COMMON PATH OF EGRESS TRAVEL ON THE
 DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]