Date Text
2007-09-27 13:08:37REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE SUBMITTED REVISED GAS ISOMETRIC RISER DIAGRAM
 IS NOT SIZED CORRECTLY PER TABLES 402.4(2) AND
 402.4(20). THE GAS PIPING NEEDS TO BE INCREASED TO
 1-1/2".
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: DELIVERY PRESSURE IS NOT INDICATED ON THE
 REVISION. APPROVED PERMIT COPY INDICATES 0.5 PSI.
  
 END OF COMMENTS:
  