Date |
Text |
2008-02-27 15:07:01 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| REVISION DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH |
| REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION |
| 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. |
| NOTE: A TRANSMITTAL LETTER IS HELPFUL. |
| |
| 2. VALUE FOR THE JOB NEEDS TO BE INCREASED AND FEES |
| PAID BEFORE REVISION IS RESUBMITTED FOR PLAN REVIEW DO |
| TO THE ADDITION OF PIPING (40' OF 1/2"CSST, 30' OF |
| 3/4" CSST, 10' OF 1/2" GALV.), FITTINGS (1- |
| 1-1/4"X1/2"X1" TEE, 1/2" TEE, 1/2" 90), 1 MAXITROL |
| REGULATOR, SHUT OFF VALVES, LABOR, ECT.... PER CITY OF |
| WPB AMENDMENTS TO CHAPTER 1, SECTION 108.3 BUILDING |
| PERMIT VALUATION. |
| |
| 3. THE REVISED GAS ISOMETRIC RISER DIAGRAM IS MISSING |
| THE IDENTIFICATION AND BTU'S FOR THE POOL HEATER. PER |
| CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. A SHUT OFF VALVE IS REQUIRED BEFORE THE MP |
| REGULATOR FOR THE PROPOSED FIREPLACE. PER FBC-2004 FUEL |
| GAS, SECTION 409.4 MP REGULATOR VALVES: A LISTED |
| SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| EACH MP REGULATOR. |
| |
| 5. SEE RED LINE CORRECTIONS TO THE CSST (THE 25' OF |
| 1/2" CSST TO THE RANGE AND PROPOSED FIRE PLACE NEEDS TO |
| BE 3/4") AND GALV (FEED FROM METER NEEDS TO BE |
| INDICATED AS 1-1/4" GALV.) BECAUSE OF THE REVISED |
| LONGEST LENGTH AND TOTAL BTU LOAD. PER FBC FUEL GAS |
| TABLES 402.4(3) AND 402.4(17). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |