Plan Review Notes
Plan Review Notes For Permit 07080439
Permit Number 07080439
Review Stop E
Sequence Number 3
Notes
Date Text
2007-11-30 08:40:09** REDLINED PLANS.
  
 1) NOTE: LOAD CALCULATIONS STILL INDICATE AC HEAT LOAD
 *AT 100 PERCENT OR 40 PERCENT. THE LOAD WAS FIGURED
 CORRECTLY HOWEVER PLANS STILL SHOW 40 PERCENT WHICH IS
 NOT PERMITTED IN THE CODE.
  
 2) NOTE: PLEASE SEE MISPRINT NOW FOR CONDUCTORS FOR
 SERVICE. SHOWS A DIFFERENT SYMBOL FOR THE 2/0 AND 1/0.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717