Notes |
Date |
Text |
2007-11-30 08:40:09 | ** REDLINED PLANS. | | | | 1) NOTE: LOAD CALCULATIONS STILL INDICATE AC HEAT LOAD | | *AT 100 PERCENT OR 40 PERCENT. THE LOAD WAS FIGURED | | CORRECTLY HOWEVER PLANS STILL SHOW 40 PERCENT WHICH IS | | NOT PERMITTED IN THE CODE. | | | | 2) NOTE: PLEASE SEE MISPRINT NOW FOR CONDUCTORS FOR | | SERVICE. SHOWS A DIFFERENT SYMBOL FOR THE 2/0 AND 1/0. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|