2007-10-31 11:43:17 | |
| ** DENIED 2ND REVIEW** |
| |
| ** PLEASE SEE NOTES FROM PREVIOUS REVIEW. |
| |
| 1) NOTE: AS STATED ON PREVIOUS REVIEW, ALL CURRENT |
| RELEVANT CODES SHALL BE STATED ON PLANS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2004 FBC W/2006 REVS. |
| |
| 2) NOTE: THE VALUE WAS CHANGED ON PERMIT APPLICATION |
| PER RE-SUB COVER SHEET. THIS WAS NOT CHANGED ON |
| APPLICATION BY CONTRACTOR ONLY ON RE-SUB COVER SHEET. |
| ** THIS IS NOTED FOR INFORMATIONAL PURPOSE TO |
| CONTRACTOR ONLY. |
| |
| 3) NOTE: PLEASE SEE CIRCUITING ON PANEL SCHEDULE |
| SUBMITTED IS NOT ACCEPTABLE USING *GENERAL LIGHTS* AND |
| *RECEPTACLES*. |
| PLEASE SEE 408.4 AND THE FOLLOWING TEXT EXTRACTED FROM |
| COMMENTARY. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4, FBC 106.1.2 |
| |
| 4) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| DETECTION DEVICES. THESE ARE SHOWN AS SD FOR SMOKE |
| DETECTORS. IF THESE ARE SMOKE DETECTORS BY DEFINITION, |
| PLEASE INCLUDE SYSTEM WHICH INCLUDE FIRE ALARM PANEL, |
| HORN DEVICES ETC. |
| IF THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AND |
| ALARM, PLEASE ADJUST TO SA. |
| PLEASE ALSO SEE THE STUDY WHICH IS AN ADAPTABLE |
| SLEEPING ROOM IS REQUIRED TO CONTAIN SMOKE DETECTION |
| DEVICE INSIDE AND OUTSIDE THIS ROOM. |
| NFPA-72 , 11.5.1.1.1, 11.8.3 |
| |
| 5) NOTE: PLEASE CLARIFY 210.12 FOR ARC FAULT |
| PROTECTION. PLEASE LIST. |
| |
| 6) NOTE: RISER INDICATES *OPTIONAL* FOR REQUIRED |
| ELECTRICAL CODE ITEMS. |
| PLANS MAY NOT CONTAIN *OPTIONAL* FOR FINAL RECORD SETS |
| OF DRAWINGS. THE DOCUMENT MUST SHOW AN ACCURATE RECORD |
| OF WORK DONE/INSTALLED. |
| FBC 106.1.2, 106.5, 110.1.2 ETC. |
| |
| 7) NOTE: PLEASE ALSO THE EQUIPMENT GROUNDING CONDUCTOR |
| IS LISTED AS *OPTIONAL* BEFORE AND AFTER MAIN. PLEASE |
| SEE 250.6, 250.24B AS AN EQUIPMENT GROUNDING CONDUCTOR |
| IS REQUIRED AFTER THE FIRST MEANS OF DISCONNECTAND |
| SHALL NOT BE INSTALLED BEFORE THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 8) NOTE: PLANS SHOW HOT WATER HEATER AS BEING PLUGGED |
| IN WHICH IS NOT PERMITTED. |
| 422.30, 422.31 |
| |
| 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| KITCHEN COUNTER SPACE SHALL BE GFI. |
| |
| 10) NOTE: PLEASE BE SURE PLANS ARE DETAILED TO ALL |
| ITEMS WHICH ARE GOING TO BE NEW AND WHICH ARE GOING TO |
| REMAIN AS EXISTING. AS THE SCOPE OF WORK APPEARS THE |
| ENTIRE HOUSE IS BEING REWIRED, MUST COMPLY WITH CURRENT |
| NEC 2005 ETC AS NOTED ABOVE. |
| THERE ARE ITEMS WHICH COULD NOT BE COMMENTED ON AS THE |
| SCOPE OF WORK IS NOT CLEARLY DEFIED. |
| |
| 11) NOTE: PLEASE INCLUDE THE TYPE OF RECESSED LIGHTING |
| FIXTURES TO MEET FBC 13-606.1.ABC.1.2.4 |
| |
| 12) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH |
| ARE NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE COORDINATE |
| AND COMPLETE. |
| FOR EXAMPLE: RECESSED LIGHTS, WATER HEATER ETC. FBC |
| 106.1.2 ADDITIONAL INFORMATION/COORDINATION. |
| |
| 13) NOTE: PANEL SCHEDULE INDICATES A SPRINKLER PUMP |
| HOWEVER THERE IS NO PUMP AND DISCONNECT ON PLANS. |
| PLEASE SHOW. FBC 106.1.2, 106.3.5.4 |
| |
| 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON |
| PANEL SCHEDULE WHICH SHOW #2 FOR THE WIRE SIZE. THIS |
| APPEARS TO BE A MISPRINT FOR #12? |
| 408.4, 310.16, FBC 106.1.2, 106.3.5.4 |
| |
| 15) NOTE: PLEASE SEE MISSING RECEPTACLE(S) ALONG |
| COUNTER SPACE AS REQUIRED PER 210.52C1 (DISHWASHER |
| COUNTER). |
| |
| 16) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52. |
| |
| 2FT OR MORE OF WALL SPACE. |
| |
| 17) NOTE: PLEASE SEE NEC 220 AS THE HEAT LOAD ON |
| CALCULATIONS MENTIONS TO BE DONE AT 100 PERCENT OR 40 |
| PERCENT. WHERE DOES THE CODE PERMIT THIS TO BE DONE AT |
| 40 PERCENT FOR THIS DWELLING UNIT FOR ONE A/C SYSTEM? |
| PLEASE SEE 220, 220.60, 220.80 ETC. |
| |
| 18) NOTE: PLEASE SEE 210.70 AND LS 101 7.8 AS A LIGHT |
| FIXTURE OF SOME TYPE WILL BE REQUIRED AT THE REAR |
| EGRESS. |
| |
| 19) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE |
| NOOK RECEPTACLES SHALL BE PART OF ONE OR *MORE* OF THE |
| SMALL APPLIANCE CIRCUITS. THIS AREA IS THE SAME AS THE |
| DINING ROOM WHICH INDICATES THE ADDITIONAL CIRCUIT WITH |
| LOAD AT 1500VA. |
| |
| |
| ** AS THERE ARE SOME ITEMS NOT YET ON PLANS AND OR |
| SHOWN THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |