Plan Review Notes For Permit 07080439
Permit Number 07080439
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-31 11:43:17 
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: AS STATED ON PREVIOUS REVIEW, ALL CURRENT
 RELEVANT CODES SHALL BE STATED ON PLANS.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC W/2006 REVS.
  
 2) NOTE: THE VALUE WAS CHANGED ON PERMIT APPLICATION
 PER RE-SUB COVER SHEET. THIS WAS NOT CHANGED ON
 APPLICATION BY CONTRACTOR ONLY ON RE-SUB COVER SHEET.
 ** THIS IS NOTED FOR INFORMATIONAL PURPOSE TO
 CONTRACTOR ONLY.
  
 3) NOTE: PLEASE SEE CIRCUITING ON PANEL SCHEDULE
 SUBMITTED IS NOT ACCEPTABLE USING *GENERAL LIGHTS* AND
 *RECEPTACLES*.
 PLEASE SEE 408.4 AND THE FOLLOWING TEXT EXTRACTED FROM
 COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4, FBC 106.1.2
  
 4) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES. THESE ARE SHOWN AS SD FOR SMOKE
 DETECTORS. IF THESE ARE SMOKE DETECTORS BY DEFINITION,
 PLEASE INCLUDE SYSTEM WHICH INCLUDE FIRE ALARM PANEL,
 HORN DEVICES ETC.
 IF THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AND
 ALARM, PLEASE ADJUST TO SA.
 PLEASE ALSO SEE THE STUDY WHICH IS AN ADAPTABLE
 SLEEPING ROOM IS REQUIRED TO CONTAIN SMOKE DETECTION
 DEVICE INSIDE AND OUTSIDE THIS ROOM.
 NFPA-72 , 11.5.1.1.1, 11.8.3
  
 5) NOTE: PLEASE CLARIFY 210.12 FOR ARC FAULT
 PROTECTION. PLEASE LIST.
  
 6) NOTE: RISER INDICATES *OPTIONAL* FOR REQUIRED
 ELECTRICAL CODE ITEMS.
 PLANS MAY NOT CONTAIN *OPTIONAL* FOR FINAL RECORD SETS
 OF DRAWINGS. THE DOCUMENT MUST SHOW AN ACCURATE RECORD
 OF WORK DONE/INSTALLED.
 FBC 106.1.2, 106.5, 110.1.2 ETC.
  
 7) NOTE: PLEASE ALSO THE EQUIPMENT GROUNDING CONDUCTOR
 IS LISTED AS *OPTIONAL* BEFORE AND AFTER MAIN. PLEASE
 SEE 250.6, 250.24B AS AN EQUIPMENT GROUNDING CONDUCTOR
 IS REQUIRED AFTER THE FIRST MEANS OF DISCONNECTAND
 SHALL NOT BE INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
  
 8) NOTE: PLANS SHOW HOT WATER HEATER AS BEING PLUGGED
 IN WHICH IS NOT PERMITTED.
 422.30, 422.31
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI.
  
 10) NOTE: PLEASE BE SURE PLANS ARE DETAILED TO ALL
 ITEMS WHICH ARE GOING TO BE NEW AND WHICH ARE GOING TO
 REMAIN AS EXISTING. AS THE SCOPE OF WORK APPEARS THE
 ENTIRE HOUSE IS BEING REWIRED, MUST COMPLY WITH CURRENT
 NEC 2005 ETC AS NOTED ABOVE.
 THERE ARE ITEMS WHICH COULD NOT BE COMMENTED ON AS THE
 SCOPE OF WORK IS NOT CLEARLY DEFIED.
  
 11) NOTE: PLEASE INCLUDE THE TYPE OF RECESSED LIGHTING
 FIXTURES TO MEET FBC 13-606.1.ABC.1.2.4
  
 12) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH
 ARE NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE COORDINATE
 AND COMPLETE.
 FOR EXAMPLE: RECESSED LIGHTS, WATER HEATER ETC. FBC
 106.1.2 ADDITIONAL INFORMATION/COORDINATION.
  
 13) NOTE: PANEL SCHEDULE INDICATES A SPRINKLER PUMP
 HOWEVER THERE IS NO PUMP AND DISCONNECT ON PLANS.
 PLEASE SHOW. FBC 106.1.2, 106.3.5.4
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON
 PANEL SCHEDULE WHICH SHOW #2 FOR THE WIRE SIZE. THIS
 APPEARS TO BE A MISPRINT FOR #12?
 408.4, 310.16, FBC 106.1.2, 106.3.5.4
  
 15) NOTE: PLEASE SEE MISSING RECEPTACLE(S) ALONG
 COUNTER SPACE AS REQUIRED PER 210.52C1 (DISHWASHER
 COUNTER).
  
 16) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52.
  
 2FT OR MORE OF WALL SPACE.
  
 17) NOTE: PLEASE SEE NEC 220 AS THE HEAT LOAD ON
 CALCULATIONS MENTIONS TO BE DONE AT 100 PERCENT OR 40
 PERCENT. WHERE DOES THE CODE PERMIT THIS TO BE DONE AT
 40 PERCENT FOR THIS DWELLING UNIT FOR ONE A/C SYSTEM?
 PLEASE SEE 220, 220.60, 220.80 ETC.
  
 18) NOTE: PLEASE SEE 210.70 AND LS 101 7.8 AS A LIGHT
 FIXTURE OF SOME TYPE WILL BE REQUIRED AT THE REAR
 EGRESS.
  
 19) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE
 NOOK RECEPTACLES SHALL BE PART OF ONE OR *MORE* OF THE
 SMALL APPLIANCE CIRCUITS. THIS AREA IS THE SAME AS THE
 DINING ROOM WHICH INDICATES THE ADDITIONAL CIRCUIT WITH
 LOAD AT 1500VA.
  
  
 ** AS THERE ARE SOME ITEMS NOT YET ON PLANS AND OR
 SHOWN THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717