2007-08-31 15:25:23 | |
| |
| ** DENIED** |
| |
| |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR |
| SHOWING NEW OR EXISTING ELECTRICAL MEETING CURRENT |
| NFPA-70 NEC, NFPA-72 AND NFPA-101. |
| PLEASE ALSO SEE FBC 2004 W/2006 REVISIONS. |
| THE PLANS SUBMITTED COMPARE TO THE FLOOR LAYOUT OF THE |
| EXISTING *SALES OFFICES* IS COMPLETELY DIFFERENT. |
| PLEASE SEE FBC 106.3.5.4 AND CODES NOTED ABOVE FOR ALL |
| ELECTRICAL TO COMPLY WITH THE CURRENT CODES ALSO BASED |
| ON THE CHANGE IN OCCUPANCY. |
| ** SOME ASPECTS OF THE BUILDING OR STRUCTURE MAY |
| ALREADY COMPLY FOR THE ELECTRICAL CODE AND FBC FOR |
| RESIDENCE. |
| |
| 2) NOTE: PLEASE KNOW WHEN SUBMITTING PLANS, PLEASE BE |
| SURE ALL PLANS ARE SIGNED, DATED AND SEALED BY THE |
| RESPECTIVE DESIGNER(S) OF RECORD AS REQUIRED PER FS 481 |
| AND 471 |
| |
| 3) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED FOR THE |
| CHANGE AND SCOPE IS COMPLETELY DIFFERENT THAN THE |
| PERMIT APPLICATION, THE VALUE FOR THE COMPLETE SCOPE OF |
| WORK SHALL COMPLY WITH THE FBC 108.3 TO INCLUDE ALL |
| LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC AS STATED |
| IN THE CODE. |
| MINIMUM VALUATION TABLES MAY BE USED FOR SCOPE OF WORK |
| AS SHOWN ON PLANS AND MAY ALSO BE ADJUSTED BY THIS |
| OFFICE ONCE THE ACTUAL COMPLETE SCOPE HAS BEEN |
| DETERMINED. |
| |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |