2007-08-31 15:25:23 
  
 ** DENIED**
  
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 SHOWING NEW OR EXISTING ELECTRICAL MEETING CURRENT
 NFPA-70 NEC, NFPA-72 AND NFPA-101.
 PLEASE ALSO SEE FBC 2004 W/2006 REVISIONS.
 THE PLANS SUBMITTED COMPARE TO THE FLOOR LAYOUT OF THE
 EXISTING *SALES OFFICES* IS COMPLETELY DIFFERENT.
 PLEASE SEE FBC 106.3.5.4 AND CODES NOTED ABOVE FOR ALL
 ELECTRICAL TO COMPLY WITH THE CURRENT CODES ALSO BASED
 ON THE CHANGE IN OCCUPANCY.
 ** SOME ASPECTS OF THE BUILDING OR STRUCTURE MAY
 ALREADY COMPLY FOR THE ELECTRICAL CODE AND FBC FOR
 RESIDENCE.
  
 2) NOTE: PLEASE KNOW WHEN SUBMITTING PLANS, PLEASE BE
 SURE ALL PLANS ARE SIGNED, DATED AND SEALED BY THE
 RESPECTIVE DESIGNER(S) OF RECORD AS REQUIRED PER FS 481
 AND 471
  
 3) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED FOR THE
 CHANGE AND SCOPE IS COMPLETELY DIFFERENT THAN THE
 PERMIT APPLICATION, THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL COMPLY WITH THE FBC 108.3 TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC AS STATED
 IN THE CODE.
 MINIMUM VALUATION TABLES MAY BE USED FOR SCOPE OF WORK
 AS SHOWN ON PLANS AND MAY ALSO BE ADJUSTED BY THIS
 OFFICE ONCE THE ACTUAL COMPLETE SCOPE HAS BEEN
 DETERMINED.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]