Text |
2008-12-05 14:44:04 | |
| ** FAILED REVIEW 5TH TIME. ** |
| |
| ** A CALL WAS PLACED TO THE ELECTRICAL ENGINEER AND |
| LEFT MESSAGE ON VOICE-MAIL TO RETURN CALL AS SOON AS |
| POSSIBLE TO GO OVER NOTE BELOW. |
| |
| 1) NOTE: THE SUBMITTED FLA-COM CALCULATIONS ARE NOW |
| METHOD*B* WHICH IS DIFFERENT FROM PREVIOUS SUBMITTED |
| CALCULATIONS. PLEASE SEE SECTION 13-400.B.3 OF THE |
| FLORIDA BUILDING CODE. THE VERSION SUBMITTED IS NOT |
| ADOPTED BY THE STATE OF FLORIDA. THIS HAS BEEN |
| DISCUSSED AND CONFIRMED ON MORE THAN ONE OCCASION WITH |
| MO MADANI WITH DEPARTMENT OF COMMUNITY AFFAIRS. THE |
| ADOPTED VERSION IS 2.5. |
| PLEASE SEE THE FOLLOWING WORDING WHICH IS TAKEN |
| DIRECTLY FROM THE ENERGY GAUGE WEBSITE. PLEASE BE SURE |
| TO READ THE LAST LINE IN PARENTHESIS. YOU WILL SEE IT |
| STATES **VERSION 2.5**. |
| IT IS IMPORTANT TO KNOW THAT IT IS THE UNDERSTANDING TO |
| THIS OFFICE THAT THERE IS A FREE PATCH ON THEIR WEBSITE |
| IN ORDER TO OBTAIN CORRECT VERSION. IT IS ALSO THE |
| UNDERSTANDING OF THIS REVIEWER/OFFICE FROM NUMEROUS |
| OTHER DESIGNERS WHO HAVE HAD TO DO THIS IS THERE IS NO |
| FEE ASSOCIATED WITH PATCH. |
| |
| ***BUILDING OFFICIALS: ENERGYGAUGE SUMMIT VERSION 3.00 |
| THROUGH 3.14 SATISFIES THE REQUIREMENTS IN 13-400.3.A |
| AND 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER |
| PROGRAM, VERSION 2.5).*** |
| |
| |
| |
| |
| THERE WILL BE COMMENTS FROM OTHER TRADES WITH RESPECT |
| TO OTHER COMPONENTS ON THE INPUT DATA REPORT OF THE |
| SUBMITTED CALCULATIONS. AS A *HEADS-UP* TO OTHER |
| POSSIBLE CONFLICTS PLEASE SEE THE OTHER |
| ITEMS/COMPONENTS WHICH ARE NOT PLACED IN THE IDR AS |
| REQUIRED. |
| METHOD *B* IS FOR ENVELOP TRADE-OFF COMPLIANCE. |
| |
| A) TYPE OF ROOF IS NOT CALLED OUT IT SIMPLY STATES |
| *ROOF* UNDER TYPE OF ROOF. |
| B) NO FLOORS IN THE IDR. |
| C) NO INFORMATION ON HOT WATER PIPE INSULATION. |
| ETC. |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |