2008-10-20 15:32:25*****UNSAT*****
  
 "THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:"
  
 9. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. ADD
 COMMENT TO SHEET FS-2
  
 "THE FOLLOWING NEW COMMENT STILL NEEDS TO BE
 ADDRESSED:"
  
 C. ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE
 FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER &
 SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST PALM
 BEACH FIRE PREVENTION AND WATER SUPPLY CHARACTERISTICS
 AS PER CITY OF WEST PALM BEACH WATER UTILITIES
 DEPARTMENT.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  