Date |
Text |
2008-10-03 15:50:43 | |
| ** DENIED 4TH REVIEW ** |
| 3RD REVIEW UNDER PERMIT APPLICATION. |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED FORM *C* IS NOT IN |
| COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1,.1.2, |
| .1.3. |
| THE FORM *C* NOW NOTES THREE SEPARATE SPACES WHICH MAY |
| NOT BE USED AS FORM *C* IS FOR A SPECIFIC USE OR |
| OCCUPANCY. IF USING A SPACE BY SPACE THEN TABLE *B* IS |
| REQUIRED TO BE USED. PLEASE SEE THE SECTIONS ABOVE |
| ALONG WITH SECTION 202 OF CHAPTER 13 FOR THE |
| DEFINITIONS OF A RENOVATION. THE FORM *C* DOES NOT SHOW |
| COMPLIANCE FOR EXTERIOR LIGHTING AS NOTED IN |
| 13-415.2.ABC.1.3 NOTED INALL REVIEWS. |
| COMPLIANCE WITH THE SPECIFIC CODES ABOVE HAS NOT BEEN |
| DEMONSTRATED. THE RESPONSE LETTER MENTIONS THIS IS NOT |
| AN ELECTRICAL COMMENT. HOWEVER PLEASE SEE STATEMENTS |
| ISSUED BY THE FLORIDA BUILDING COMMISSION WHICH ARE |
| AVAILABLE ON-LINE WHICH STATE: * THE INTENT FOR REVIEW |
| OF THE CALCULATIONS AND CHAPTER 13 IS FOR EACH TRADE |
| REVIEWER TO REVIEW THAT PARTICULAR TRADE. |
| A CALLED WAS PLACED TO THE ELECTRICAL ENGINEER AS OF |
| THIS REVIEW AND A MESSAGE WAS LEFT ON VOICEMAIL TO |
| RETURN CALL. |
| THE CALCULATIONS ON FORM *C* AS SUBMITTED ALONG WITH |
| ELECTRICAL PLANS WILL BE RETAINED BY THIS OFFICE. |
| BASED ON THE *C* SUBMITTED AND OCCUPANCY DESIGN WATTAGE |
| IS OVER THE ALLOWANCES PERMITTED. THIS IS NOT |
| LODGE/HOTEL/TRANSIENT LODGING. THIS IS A ASSEMBLY |
| OCCUPANCY BASED ON ARCHITECTURAL PLANS OCCUPANCY |
| DESIGNATION. PLEASE CONTACT THIS OFFICE/REVIEW TO GO |
| OVER HOWEVER THE CODE COMPLIANCE CAN BE SHOWN. |
| |
| |
| 2) NOTE: PLEASE SEE THE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENT FOR CODE COMPLIANCES. THE SPECIFIC |
| SECTIONS OF THE CODE HAVE BEEN GIVEN NOW FOR FOUR |
| REVIEWS THREE OF WHICH ARE UNDER PERMIT APPLICATION. |
| THE STATUTORY REQUIREMENT IS THAT A FEE BE ASSESSED. |
| THIS IS NOT A LOCAL ORDINANCE, REGULATION, OR |
| ADMINISTRATIVE AMENDMENT. THIS IS A FLORIDA STATUTE |
| REQUIRED FEE. THIS OFFICE HAS PLACED THE CONTACT |
| INFORMATION FOR ANY QUESTIONS OR COMMENTS ON ALL |
| REVIEWS TO GO OVER PLANS HOWEVER CONTACT HAS NOT YET |
| BEEN MADE. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |