Plan Review Notes For Permit 07080406 |
Permit Number |
07080406 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-05-01 14:08:03 | ***DENIED*** | | | | MOST OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE | | THE FOLLOWING PAST COMMENTS AND A NEW COMMENT: | | | | 9) KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE | | DEPARTMENT CONNECTIONS. FOR APPLICATIONS, CONTACT WEST | | PALM BEACH FIRE PREVENTION BURAEU AT (561) 804-4724. | | ADD COMMENT TO SHEET FS-2. | | | | B) PLEASE EXPLAIN THE ADDITION OF APT. 101 IN THE | | PROJECT SITE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | C) ON SHEET FS-2, REFERENCES ARE MADE TO MIAMI DADE | | FIRE RESCUE DEPARTMENT AND MIAMI AND MIAMI-DADE WATER | | AND SEWER. PLEASE PROVIDE FLOW TEST DATA AS PER WEST | | PALM BEACH FIRE PREVENTION AND WATER SUPPLY | | CHARACTERISTICS AS PER CITY OF WEST PALM BEACH WATER | | UTILITIES DEPARTMENT. | | | | NEW COMMENT: | | | | 1) SHEET CS 100 REFERENCES SPRINKLER SYSTEM TO COMPLY | | WITH 2004 NFPA 101, SECTION 9.7. NOTE SHOULD REFERENCE | | 2003 EDITION. | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | ADDRESSED. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|