2008-04-03 18:43:28** DENIED 3RD REVIEW **
 ** ONLY 2ND REVIEW UNDER ACTUAL PERMIT APPLICATION.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON CHANGES MADE TO PLANS AND/OR
 DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 FOR COMMERCIAL PORTION OF BUILDING NEEDS TO MEET CODE
 AND COORDINATE WITH PLANS. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 FOR EXAMPLE:
 PLEASE BE SURE TO SEE THE CALCULATIONS STATED ON SHEET
 E-3 STATES THIS BUILDING AS A "LODGE". HOW IS THIS
 POSSIBLE? THE SUBMITTED ENERGY CALCULATIONS CLEARLY
 STATE "OFFICE".
 FOR EXAMPLE:
 PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT SHOW
 ANY EXTERIOR LIGHT FIXTURES YET THE PLANS CLEARLY SHOW
 EXTERIOR LIGHTING. HOW IS THIS POSSIBLE?
 FOR EXAMPLE:
 PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE SHOWN FOR
 FIRST FLOOR ZONE HOWEVER THE PLANS CONTAINS A MINIMUM
 OF FOUR DIFFERENT TYPES OF FIXTURES. (THIS IS NOT
 NOTING THE SEPARATE ELEVATOR ZONE)
 FOR EXAMPLE:
 PLEASE SEE UPPER FLOOR ZONE FOR AHU3. WHERE ARE K
 FIXTURES, WHERE ARE THE FIXTURES IN BATHROOMS SHOWN FOR
 SHOWERS? WHERE ARE THE WALL SCONCES?
  
 ** PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEET WHEN RESUBMITTING. FBC 13-103.1
  
 2) NOTE: PLEASE SEE THE TAPPED CONDUCTORS FROM THE
 320AMP METER CAN SHALL TERMINATE IN OVER CURRENT
 PROTECTION HOWEVER THE RISER ONLY SHOWS A 30AMP 2-POLE
 DISCONNECT AT BOTH THE SERVICE MAIN LOCATION AND THE
 ELEVATOR DISCONNECT.
 PLEASE KNOW THE FIRST ITEM IS THIS 30AMP DISCONNECT IS
 ONE OF THE SERVICE MAINS YET NO LABELING OF THIS IS
 SHOWN. 230.2E (ALL)
 PLEASE SEE THE SECOND ITEM IS THAT THIS 30AMP
 DISCONNECT SHALL BE SERVICE EQUIPMENT RATED AND SERVICE
 ENTRANCE RATED FOR A MAIN. 230.70, 230.71, 110.7, 90.7
 PLEASE VERIFY THIS.
 PLEASE SEE FOR THE THIRD ITEM; PLEASE SEE 240.21,
 310.16 AND 240.4 AS THE TAPPED CONDUCTORS SHALL
 TERMINATE IN OVER CURRENT PROTECTION.
  
 3) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN
 ON ELECTRICAL PANEL SCHEDULES AND MECHANICAL PLANS ARE
 NOT CODE COMPLIANT.
 PLEASE SEE THE CODE REQUIRES MINIMUM OVER CURRENT
 PROTECTION OF 125% PER 424.3B. PLEASE SEE ONE OF THE
 5KW AH UNITS STATES 60AMP OCP.
 PLEASE SEE THE AC SHEETS AS THESE STATES THE MINIMUM
 CIRCUIT AMPACITY OF THE 5KW UNITS IS 13AMPS AND THE MAX
 OCP ID 20AMPS. THIS CAN NOT BE POSSIBLE AS THE LOAD OF
 5KW AT 240V IS OVER 20AMPS. THIS IS BEFORE THE MINIMUM
 125% WHICH IS REQUIRED BY CODE.
 PLEASE SEE THE UNIT WHICH SHOWS A 12.9 KW HEAT STRIP
 SHOWS MINIMUM CIRCUIT LOAD OF 20AMPS AND THE MAXIMUM
 OCP AT 40AMPS. THIS IS ALSO NOT POSSIBLE AS THE LOAD ON
 THIS UNIT BEFORE 125% IS SUBSTANTIALLY HIGHER THAN THE
 40AMP BREAKER OR CIRCUIT.
 PLEASE SEE 424.3B, 240.4, 310.16 ETC.
  
 ** PLEASE SEE THE ARCHITECTURAL PLANS STATE AND SHOW A
 AHU #4, WHEREAS THE MECHANICAL PLANS SHOWS THE AHU#3 IN
 THE SAME LOCATION.
  
 4) NOTE: PLEASE SEE THE MINIMUM PHOTO-METRIC LEVELS ON
 THE OUTSIDE STAIRS DO NOT MEET THE LIFE SAFETY CODE FOR
 COMPLIANCE.
 PLEASE SEE 7.8.1.3 AS THIS REQUIRES A *MINIMUM* OF
 10FOOT CANDLES. THE PLANS SHOWS ABOUT HALF OF THE
 NEEDED FOR NORMAL LIGHTING LEVELS.
  
 5) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS NOW
 BEING GIVEN. THERE ARE REPEAT COMMENTS FOR CODE
 COMPLIANCE WHICH HAS BEEN MADE ON THE LAST TWO REVIEWS
 WHICH ARE BEING REPEATED ONCE AGAIN. THE INITIAL REVIEW
 DOES NOT APPLY AS PLANS WERE ONLY SUBMITTED FOR *PLAN
 REVIEW* AND WERE NOT SUBMITTED FOR PERMIT APPLICATION.
  
 PLEASE BE SURE ALL COMMENTS ARE ADDRESSED ON THE THIRD
 REVIEW UNDER PERMIT AND FORTH REVIEW FOR PROJECT. ONCE
 AGAIN AS STATED ON PREVIOUS REVIEWS IF THERE ARE
 QUESTIONS OR COMMENTS PLEASE CONTACT THIS REVIEWER.
 PLANS AND CALCULATIONS MAY BE RETAINED BY THIS OFFICE
 DUE TO THE REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  