Date |
Text |
2008-04-03 18:43:28 | ** DENIED 3RD REVIEW ** |
| ** ONLY 2ND REVIEW UNDER ACTUAL PERMIT APPLICATION. |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| COMMENTS BASED ON CHANGES MADE TO PLANS AND/OR |
| DOCUMENTS SUBMITTED. |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| FOR COMMERCIAL PORTION OF BUILDING NEEDS TO MEET CODE |
| AND COORDINATE WITH PLANS. PLEASE BE SURE TO SEE |
| 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| FOR EXAMPLE: |
| PLEASE BE SURE TO SEE THE CALCULATIONS STATED ON SHEET |
| E-3 STATES THIS BUILDING AS A "LODGE". HOW IS THIS |
| POSSIBLE? THE SUBMITTED ENERGY CALCULATIONS CLEARLY |
| STATE "OFFICE". |
| FOR EXAMPLE: |
| PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT SHOW |
| ANY EXTERIOR LIGHT FIXTURES YET THE PLANS CLEARLY SHOW |
| EXTERIOR LIGHTING. HOW IS THIS POSSIBLE? |
| FOR EXAMPLE: |
| PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE SHOWN FOR |
| FIRST FLOOR ZONE HOWEVER THE PLANS CONTAINS A MINIMUM |
| OF FOUR DIFFERENT TYPES OF FIXTURES. (THIS IS NOT |
| NOTING THE SEPARATE ELEVATOR ZONE) |
| FOR EXAMPLE: |
| PLEASE SEE UPPER FLOOR ZONE FOR AHU3. WHERE ARE K |
| FIXTURES, WHERE ARE THE FIXTURES IN BATHROOMS SHOWN FOR |
| SHOWERS? WHERE ARE THE WALL SCONCES? |
| |
| ** PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON THE |
| CERTIFICATION SHEET WHEN RESUBMITTING. FBC 13-103.1 |
| |
| 2) NOTE: PLEASE SEE THE TAPPED CONDUCTORS FROM THE |
| 320AMP METER CAN SHALL TERMINATE IN OVER CURRENT |
| PROTECTION HOWEVER THE RISER ONLY SHOWS A 30AMP 2-POLE |
| DISCONNECT AT BOTH THE SERVICE MAIN LOCATION AND THE |
| ELEVATOR DISCONNECT. |
| PLEASE KNOW THE FIRST ITEM IS THIS 30AMP DISCONNECT IS |
| ONE OF THE SERVICE MAINS YET NO LABELING OF THIS IS |
| SHOWN. 230.2E (ALL) |
| PLEASE SEE THE SECOND ITEM IS THAT THIS 30AMP |
| DISCONNECT SHALL BE SERVICE EQUIPMENT RATED AND SERVICE |
| ENTRANCE RATED FOR A MAIN. 230.70, 230.71, 110.7, 90.7 |
| PLEASE VERIFY THIS. |
| PLEASE SEE FOR THE THIRD ITEM; PLEASE SEE 240.21, |
| 310.16 AND 240.4 AS THE TAPPED CONDUCTORS SHALL |
| TERMINATE IN OVER CURRENT PROTECTION. |
| |
| 3) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN |
| ON ELECTRICAL PANEL SCHEDULES AND MECHANICAL PLANS ARE |
| NOT CODE COMPLIANT. |
| PLEASE SEE THE CODE REQUIRES MINIMUM OVER CURRENT |
| PROTECTION OF 125% PER 424.3B. PLEASE SEE ONE OF THE |
| 5KW AH UNITS STATES 60AMP OCP. |
| PLEASE SEE THE AC SHEETS AS THESE STATES THE MINIMUM |
| CIRCUIT AMPACITY OF THE 5KW UNITS IS 13AMPS AND THE MAX |
| OCP ID 20AMPS. THIS CAN NOT BE POSSIBLE AS THE LOAD OF |
| 5KW AT 240V IS OVER 20AMPS. THIS IS BEFORE THE MINIMUM |
| 125% WHICH IS REQUIRED BY CODE. |
| PLEASE SEE THE UNIT WHICH SHOWS A 12.9 KW HEAT STRIP |
| SHOWS MINIMUM CIRCUIT LOAD OF 20AMPS AND THE MAXIMUM |
| OCP AT 40AMPS. THIS IS ALSO NOT POSSIBLE AS THE LOAD ON |
| THIS UNIT BEFORE 125% IS SUBSTANTIALLY HIGHER THAN THE |
| 40AMP BREAKER OR CIRCUIT. |
| PLEASE SEE 424.3B, 240.4, 310.16 ETC. |
| |
| ** PLEASE SEE THE ARCHITECTURAL PLANS STATE AND SHOW A |
| AHU #4, WHEREAS THE MECHANICAL PLANS SHOWS THE AHU#3 IN |
| THE SAME LOCATION. |
| |
| 4) NOTE: PLEASE SEE THE MINIMUM PHOTO-METRIC LEVELS ON |
| THE OUTSIDE STAIRS DO NOT MEET THE LIFE SAFETY CODE FOR |
| COMPLIANCE. |
| PLEASE SEE 7.8.1.3 AS THIS REQUIRES A *MINIMUM* OF |
| 10FOOT CANDLES. THE PLANS SHOWS ABOUT HALF OF THE |
| NEEDED FOR NORMAL LIGHTING LEVELS. |
| |
| 5) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS NOW |
| BEING GIVEN. THERE ARE REPEAT COMMENTS FOR CODE |
| COMPLIANCE WHICH HAS BEEN MADE ON THE LAST TWO REVIEWS |
| WHICH ARE BEING REPEATED ONCE AGAIN. THE INITIAL REVIEW |
| DOES NOT APPLY AS PLANS WERE ONLY SUBMITTED FOR *PLAN |
| REVIEW* AND WERE NOT SUBMITTED FOR PERMIT APPLICATION. |
| |
| PLEASE BE SURE ALL COMMENTS ARE ADDRESSED ON THE THIRD |
| REVIEW UNDER PERMIT AND FORTH REVIEW FOR PROJECT. ONCE |
| AGAIN AS STATED ON PREVIOUS REVIEWS IF THERE ARE |
| QUESTIONS OR COMMENTS PLEASE CONTACT THIS REVIEWER. |
| PLANS AND CALCULATIONS MAY BE RETAINED BY THIS OFFICE |
| DUE TO THE REPEAT COMMENTS FOR CODE COMPLIANCE. |
| |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |