2008-04-22 16:25:40BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1-6) COMPLIED.
  
 7) 3RD REQUEST, ROOFING SYSTEMS- THE SUB-SYSTEM
 HIGHLIGHTED ON PAGES 14-15 LIST A MAXIMUM DESIGN
 PRESSURE OF -45 WITH LIMITATION# 7. NOTE UNDER
 LIMITATION# 7 DOES ALLOW ENHANCED FASTENING IN ZONES 2
 & 3 TO THE CALCULATION RAS 117. PLEASE HAVE YOUR DESIGN
 PROFESSIONAL PROVIDE THE RAS 117 FOR THE ENHANCED
 FASTENING IN ZONES 2& 3.
 FIRST OFF THE PROBLEM WITH THE LETTER FROM TURQUOISE
 ENGINEERING IS THIS IS A COPY NOT AN ORIGINAL SIGNED
 AND SEALED ORIGINAL. THE SECOND ISSUE WITH THE PROPERTY
 BEING IN EITHER A "B" ZONE OR "C" ZONE, YES I DID STATE
 THIS PROPERTY LIES IN A "B" ZONE BUT THE ENGINEER OF
 RECORD WOULD NEED TO CHANGE THEIR PLAN TO INDICATE A
 "B" ZONE. SHEET S100 THE STRUCTURAL DESIGNER OR
 ENGINEER JOSE A TOLEDO HAS ELECTED TO DESIGN THIS
 BUILDING TO A MORE RESTRICTIVE "C" ZONE WITH THE HIGHER
 ASSCIATED PRESSURES. MR. TOLEDO HAS ALSO USED THE
 HIGHER "C" VALUES FOR THE MOMENT OF OVER TURNING FOR
 THE CALCULATIONS FOR THE A/C UNITS. PLEASE EITHER HAVE
 THE DESIGN PROFESSIONAL IN CHARGE OF THE PROJECT CHANGE
 FROM THE CZONE AND ASSOCIATED PRESSURES OR PROVIDE RAS
 117 CALCYULATIONS FOR THE "C" ZONE. NOTE ALSO INEITHER
 CASE IF ANOTHER ENGINNER IS BROUGHT IN FOR THE ROOFING
 APPROVALS, THE ENGINEER OF RECORD WILL NEED TO REVIEW
 THE DESIGN AND CALCULATIONS BEFORE SUBMITTING TO THE
 BUILDING DEPARTMENT.
  
 8) 3RD REQUEST, SEMI-COMPLIED: HURRICANE SHUTTERS,
 SEMI- COMPLIED. PLEASE SEE THE ADDTIONAL INFORMATION
 THAT IS REQUIRED FOR USE OF STORM PANELS. A SAMPLE OF
 AN INSTALLATION SCHEDULE IS ATTACHED.
 NOTE MANY OF THE WINDOWS SUBMITTED ARE A FIN TYPE
 WINDOW THAT WILL REQUIRE THE STORM SHUTTERS TO BE SET
 AWAY FROM THE GLAZING BECAUSE OF THE DEFLECTION OF THE
 STORM PANEL DURING A HIGH WIND EVENT. HIGHLIGHT OR
 CIRCLE WHICH TYPE OF INSTALLATION WILL BE USED AND TYPE
 OF FASTENERS.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 9-21) COMPLIED.
  
 22) AGAIN SEE ELECTRICAL COMMENTS ABOUT THE ENERGY
 CALCULATIONS.
  
 23-25) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  