Date |
Text |
2008-02-08 09:36:43 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE |
| ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE |
| 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC |
| OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH |
| WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES |
| TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE |
| TOILET AND LAV IN THE STALL/COMPARTMENT. |
| ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT |
| COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE |
| W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF |
| THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF |
| THE W/C AS REQUIRED IN FIG 11-30E. |
| |
| 5. OK |
| |
| 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND |
| SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH |
| WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS |
| AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. |
| SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN |
| THE STALL/COMPARTMENT. |
| ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT |
| COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE |
| W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF |
| THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF |
| THE W/C AS REQUIRED IN FIG 11-30E. |
| |
| 7. OK |
| |
| 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| ___W/C'S |
| A. 11-4.16.5 FLUSH CONTROLS |
| ****NOT ADDRESSED |
| ___URINAL |
| A. 11-4.18.2 HEIGHT |
| ****NOT ADDRESSED |
| B. 11-4.18.3 CLEAR FLOOR SPACE |
| ****NOT ADDRESSED |
| C. 11-4.18.4 FLUSH CONTROLS |
| ****NOT ADDRESSED |
| ___ FOR LAVS |
| A. 11-4.19.5 FAUCETS |
| ___SHOWERS |
| A. 11-4.21.2 SIZE & CLEARANCES |
| ****NOT ADDRESSED, SHOWS 3'-10-5/8" |
| B. OK |
| C. OK |
| D. OK |
| C. OK |
| E. OK |
| |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| |
| 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS |
| REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL |
| OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE |
| RISER DIAGRAM. |
| ****RESPONSE NOTED, BUT THE CIVIL PLANS HAVE NOT BEEN |
| SUBMITTED. |
| |
| 14. OK |
| |
| 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT |
| DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT |
| INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 |
| INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. |
| PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO |
| INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL |
| WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL |
| CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL |
| SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION |
| 13-103. |
| ****NO RESPONSE, NOT ADDRESSED. (ALSO SEE COMMENT |
| NUMBER ONE OF THE ELECTRICAL PLAN REVIEW). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |