Plan Review Notes
Plan Review Notes For Permit 07080406
Permit Number 07080406
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-08 09:36:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE
 ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE
 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC
 OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH
 WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES
 TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE
 TOILET AND LAV IN THE STALL/COMPARTMENT.
 ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT
 COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE
 W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF
 THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF
 THE W/C AS REQUIRED IN FIG 11-30E.
  
 5. OK
  
 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND
 SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH
 WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS
 AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY.
 SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN
 THE STALL/COMPARTMENT.
 ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT
 COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE
 W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF
 THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF
 THE W/C AS REQUIRED IN FIG 11-30E.
  
 7. OK
  
 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 ___URINAL
 A. 11-4.18.2 HEIGHT
 ****NOT ADDRESSED
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED
 C. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED
 ___ FOR LAVS
 A. 11-4.19.5 FAUCETS
 ___SHOWERS
 A. 11-4.21.2 SIZE & CLEARANCES
 ****NOT ADDRESSED, SHOWS 3'-10-5/8"
 B. OK
 C. OK
 D. OK
 C. OK
 E. OK
  
 9. OK
 10. OK
 11. OK
 12. OK
  
 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL
 OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE
 RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE CIVIL PLANS HAVE NOT BEEN
 SUBMITTED.
  
 14. OK
  
 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT
 DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT
 INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3
 INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V.
 PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO
 INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL
 WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL
 CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL
 SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION
 13-103.
 ****NO RESPONSE, NOT ADDRESSED. (ALSO SEE COMMENT
 NUMBER ONE OF THE ELECTRICAL PLAN REVIEW).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved