2008-02-11 15:28:54 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1 THROUGH 4: OK |
| |
| 5. BOOSTER FAN HAS BEEN ADDED TO ACCOMMODATE NEW DRYER |
| EXHAUST OUTLET LOCATION. CLOTHES DRYERS SHALL BE |
| EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS PER FBC, M 504.1. A BOOSTER FAN MAY ONLY |
| BE USED IF ALLOWED BY DRYER MANUFACTURER?S INSTALLATION |
| INSTRUCTIONS. |
| NOTE: WHERE THE MAKE AND MODEL OF THE CLOTHES DRYER TO |
| BE INSTALLED IS KNOWN AND THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS FOR SUCH DRYER ARE PROVIDED |
| TO THE CODE OFFICIAL, THE MAXIMUM LENGTH OF THE EXHAUST |
| DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED |
| TO BE IN ACCORDANCE WITH THE DRYER MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS PER FBC 504.6.1 EXCEPTION. |
| THE DRYER MANUFACTURER MAY ALLOW DRYER DUCT LENGTHS |
| WHICH WILL MAKE A BOOSTER FAN UNNECESSARY. PROVIDE |
| MANUFACTURER?S INSTRUCTIONS. |
| |
| 6 AND 7: OK |
| |
| 8. VENTILATION RATE FOR DWELLING UNIT TO BE DETERMINED |
| PER THE RATIO OF OPENABLE WINDOW AND DOOR AREA TO FLOOR |
| AREA IN ACCORDANCE WITH FRC 303.1. PROVIDE CALCULATIONS |
| CONTAINING THIS DATA SHOWING COMPLIANCE WITH THIS |
| SECTION. ASHRAE 62-89 IS NOT APPLICABLE IN THIS |
| SITUATION UNDER THIS CODE AS IT IS NOT A REFERENCE |
| STANDARD FOR THE FRC ACCORDING TO FRC CHAPTER 43. |
| |
| 9. NO INFORMATION COULD BE FOUND ON PLANS REGARDING |
| THIS COMMENT. THIS ISSUE CAN BE ADDRESSED BY FIELD |
| INSPECTION. HOWEVER, ADDRESSING THIS NOW WITH DETAILED |
| INFORMATION COULD AVOID DELAYS AND FAILED INSPECTIONS |
| IN THE FUTURE. |
| |
| 10. WIND LOAD CALCULATIONS SUBJECT TO BUILDING PLAN |
| REVIEW. |
| |
| 11. OK |
| |
| 12. FIRESTOP DETAIL FOR REFRIGERANT PIPES SHOWN ON |
| PLANS, CAJ 1047, DOES NOT MAKE PROVISIONS FOR PIPE |
| INSULATION AND THEREFORE IS NOT APPROPRIATE FOR A |
| REFRIGERANT PIPE APPLICATION. PROVIDE A |
| THROUGH-PENETRATION FIRESTOP SYSTEM WHICH IS |
| APPROPRIATE FOR THE PIPING SYSTEM BEING USED PER FBC |
| 712.3. |
| |
| NOTE: PLEASE PROVIDE WRITTEN RESPONSE TO REVIEW |
| COMMENTS TO ASSIST IN SUBSEQUENT REVIEWS. |
| |