2008-02-11 15:28:54REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 4: OK
  
 5. BOOSTER FAN HAS BEEN ADDED TO ACCOMMODATE NEW DRYER
 EXHAUST OUTLET LOCATION. CLOTHES DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS PER FBC, M 504.1. A BOOSTER FAN MAY ONLY
 BE USED IF ALLOWED BY DRYER MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
 NOTE: WHERE THE MAKE AND MODEL OF THE CLOTHES DRYER TO
 BE INSTALLED IS KNOWN AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR SUCH DRYER ARE PROVIDED
 TO THE CODE OFFICIAL, THE MAXIMUM LENGTH OF THE EXHAUST
 DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED
 TO BE IN ACCORDANCE WITH THE DRYER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS PER FBC 504.6.1 EXCEPTION.
 THE DRYER MANUFACTURER MAY ALLOW DRYER DUCT LENGTHS
 WHICH WILL MAKE A BOOSTER FAN UNNECESSARY. PROVIDE
 MANUFACTURER?S INSTRUCTIONS.
  
 6 AND 7: OK
  
 8. VENTILATION RATE FOR DWELLING UNIT TO BE DETERMINED
 PER THE RATIO OF OPENABLE WINDOW AND DOOR AREA TO FLOOR
 AREA IN ACCORDANCE WITH FRC 303.1. PROVIDE CALCULATIONS
 CONTAINING THIS DATA SHOWING COMPLIANCE WITH THIS
 SECTION. ASHRAE 62-89 IS NOT APPLICABLE IN THIS
 SITUATION UNDER THIS CODE AS IT IS NOT A REFERENCE
 STANDARD FOR THE FRC ACCORDING TO FRC CHAPTER 43.
  
 9. NO INFORMATION COULD BE FOUND ON PLANS REGARDING
 THIS COMMENT. THIS ISSUE CAN BE ADDRESSED BY FIELD
 INSPECTION. HOWEVER, ADDRESSING THIS NOW WITH DETAILED
 INFORMATION COULD AVOID DELAYS AND FAILED INSPECTIONS
 IN THE FUTURE.
  
 10. WIND LOAD CALCULATIONS SUBJECT TO BUILDING PLAN
 REVIEW.
  
 11. OK
  
 12. FIRESTOP DETAIL FOR REFRIGERANT PIPES SHOWN ON
 PLANS, CAJ 1047, DOES NOT MAKE PROVISIONS FOR PIPE
 INSULATION AND THEREFORE IS NOT APPROPRIATE FOR A
 REFRIGERANT PIPE APPLICATION. PROVIDE A
 THROUGH-PENETRATION FIRESTOP SYSTEM WHICH IS
 APPROPRIATE FOR THE PIPING SYSTEM BEING USED PER FBC
 712.3.
  
 NOTE: PLEASE PROVIDE WRITTEN RESPONSE TO REVIEW
 COMMENTS TO ASSIST IN SUBSEQUENT REVIEWS.
  