2008-01-22 12:05:11 | |
| |
| ** DENIED 2NDREVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH |
| RESPECT TO FBC CHAPTER 13 FOR LIGHTING PERFORMANCE |
| CALCULATIONS/ENERGY CALCULATIONS. |
| PLEASE SEE ONCE AGAIN THE SUBMITTED ENERGY CALCULATIONS |
| MAY NOT BE USED AS SHOW. PLEASE SEE IN FACT THESE ARE |
| THE SAME AS PREVIOUSLY SUBMITTED. ONE SET IS FORM 600 |
| FOR WHOLE BUILDING RESIDENTIAL WHICH THIS IS NOT A |
| WHOLE RESIDENTIAL BUILDING BY DEFINITION. THIS 600A |
| FORM ALSO STATES AN ADDRESS OF 2037 SPRUCE WHICH IS NOT |
| THE BUILDING ADDRESSING OF THIS APPLIED SCOPE OF WORK. |
| PLEASE SEE THE OTHER METHOD SUBMITTED IS THE SAME |
| METHOD *A* FROM PREVIOUS REVIEW. THIS MAY ALSO NOT BE |
| USED AS SUBMITTED. |
| PLEASE SEE THE INFORMATION ON THE COVER SHEET, SUMMARY |
| SHEETS AND THE INPUT DATA REPORTS DO NOT CORRELATE WITH |
| PLANS. |
| THE AMOUNT OF LIGHT FIXTURES, THE WATTAGE, THE TYPES |
| AND THE METHOD OF CONTROLS ALL NEED TO MEET 13-415.2. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AS THE SQ FT ON |
| CALCULATIONS IS STATING THE BUILDING IS 8K PLUS SQ FT. |
| PLEASE KNOW IF A/C IS BEING ADDED, PLEASE SEE |
| MECHANICAL REVIEW COMMENTS. |
| PLEASE SUBMIT THE ABOVE INFORMATION. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED |
| COORDINATION OF ALL SERVICE ENTRANCE CONDUCTORS AND |
| FEEDERS WITH THAT OF WHICH IS SINGLE PHASE AND THREE |
| PHASE. MOST OF THESE WERE DONE BUT PLEASE SEE THERE IS |
| NO NEUTRAL CONDUCTOR BEING SHOWN TO THE ELEVATOR |
| SERVICE DISCONNECT WHICH IS REQUIRED. |
| PLEASE ADJUST THE SERVICE ENTRANCE CONDUCTORS TO THIS |
| FIRST MEANS OF DISCONNECT. |
| 230.42C, 250.24C, 250.6 ETC |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW REQUEST TO CLEARLY |
| DESIGNATE THE SMOKE DETECTION DEVICES. SYMBOL LEGEND |
| STILL CALLS FOR SMOKE DETECTORS AND THEN ALSO NOTES |
| SMOKE ALARMS. |
| PLEASE SHOW WHICH ONE AS THESE ARE DIFFERENT BY |
| DEFINITION. |
| PLEASE SEE NFPA-72 |
| |
| 4) NOTE: PLEASE SEE PREVIOUS REQUEST FOR PHOTO-METRIC |
| LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| LS 101 7.8.1.3, 7.9.2.2 |
| PLANS SEEM TO INDICATE LEVEL UNDER EMERGENCY ONLY. |
| |
| 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| SEAL NO BEING CLEAR AND VISIBLE WITH ALL INFORMATION ON |
| SAID SEAL. |
| PLEASE SEE THE LICENSE NUMBER ON SEAL IS MISSING THE |
| LAST DIGIT AND CAN NOT CLEARLY SEE THIS. |
| A LEAD RUB WAS USED AND INFORMATION WAS STILL NOT CLEAR |
| AND VISIBLE. |
| PLEASE SEE FS 471.025 AND ADJUST. |
| |
| 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |