Plan Review Notes
Plan Review Notes For Permit 07080406
Permit Number 07080406
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-14 16:47:33BUILDING PLAN REVIEW
 PERMIT: 07080406
 ADD: 2027 SPRUCE
 CONT: JAW CONSTRUCTION
 TEL: (561)333-6738
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL,PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL,106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. PLEASE INCORPORATE
 INTO PLAN DATA.
  
 2-5)COMPLIED FROM FIRST REVIEW.
  
 6) SEMI-COMPLIED. PLANS A302 INDICATE THE USE OF 1 HOUR
 FIRE RATED WINDOW SYSTEMS AT THE EXTERIOR STAIRS. THERE
 HAS BEEN NO PRODUCT APPROVAL INFORMATION SUBMITTED FOR
 THE FIRE RATED WINDOWS, NOTE THESE WINDOW WILL REQUIRE
 STORM SHUTTERS THE MANUFACTURERS DO NOT MAKE A FIRE
 RATED LARGE MISSLE RATED ASSEMBLY.
  
 7) ROOFING SYSTEMS- THE SUB-SYSTEM HIGHLIGHTED ON PAGES
 14-15 LIST A MAXIMUM DESIGN PRESSURE OF -45 WITH
 LIMITATION# 7. NOTE UNDER LIMITATION# 7 DOES ALLOW
 ENHANCED FASTENING IN ZONES 2 & 3 TO THE CALCULATION
 RAS 117. PLEASE HAVE YOUR DESIGN PROFESSIONAL PROVIDE
 THE RAS 117 FOR THE ENHANCED FASTENING IN ZONES 2& 3.
  
 8) HURRICANE SHUTTERS, SEMI- COMPLIED. PLEASE SEE THE
 ADDTIONAL INFORMATION THAT IS REQUIRED FOR USE OF STORM
 PANELS.PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.FL BLD CODE 2004 SECTION
 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9-21) COMPLIED.
  
 22) PLEASE SEE ELECTRICAL NOTES ON ENERGY
 CALCULATIONS.
  
 NEW COMMENTS
  
 23)2-29-08 COMPLIED. EXCEPTION TO 302.3.2 FOR FIRE
 SPRINKLERS 1 HR REDUCTION BUT NOT LESS THAN 1 HR.OK
  
 24) SHOWER STALLS- 11-4.23.2 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES. THE MAIN
 DOOR TO THE RESTROOM OVERLAYS THE CLEAR FLOOR SPACE
 REQUIRED FORTHE SHOWER.
  
 25) 11-4.13.7 DOORS IN SERIES PLEASE REVIEW THE
 RESTROOM ENTRY DOOR AND THE ACCESSIBLE STALL DOOR.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.