2008-02-14 16:47:33 | BUILDING PLAN REVIEW |
| PERMIT: 07080406 |
| ADD: 2027 SPRUCE |
| CONT: JAW CONSTRUCTION |
| TEL: (561)333-6738 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 1B) INFORMATIONAL,PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. |
| IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL,106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE2007 SUPPLEMENTS. PLEASE INCORPORATE |
| INTO PLAN DATA. |
| |
| 2-5)COMPLIED FROM FIRST REVIEW. |
| |
| 6) SEMI-COMPLIED. PLANS A302 INDICATE THE USE OF 1 HOUR |
| FIRE RATED WINDOW SYSTEMS AT THE EXTERIOR STAIRS. THERE |
| HAS BEEN NO PRODUCT APPROVAL INFORMATION SUBMITTED FOR |
| THE FIRE RATED WINDOWS, NOTE THESE WINDOW WILL REQUIRE |
| STORM SHUTTERS THE MANUFACTURERS DO NOT MAKE A FIRE |
| RATED LARGE MISSLE RATED ASSEMBLY. |
| |
| 7) ROOFING SYSTEMS- THE SUB-SYSTEM HIGHLIGHTED ON PAGES |
| 14-15 LIST A MAXIMUM DESIGN PRESSURE OF -45 WITH |
| LIMITATION# 7. NOTE UNDER LIMITATION# 7 DOES ALLOW |
| ENHANCED FASTENING IN ZONES 2 & 3 TO THE CALCULATION |
| RAS 117. PLEASE HAVE YOUR DESIGN PROFESSIONAL PROVIDE |
| THE RAS 117 FOR THE ENHANCED FASTENING IN ZONES 2& 3. |
| |
| 8) HURRICANE SHUTTERS, SEMI- COMPLIED. PLEASE SEE THE |
| ADDTIONAL INFORMATION THAT IS REQUIRED FOR USE OF STORM |
| PANELS.PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| GLAZING. FBC 1609.1.4.FL BLD CODE 2004 SECTION |
| 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 9-21) COMPLIED. |
| |
| 22) PLEASE SEE ELECTRICAL NOTES ON ENERGY |
| CALCULATIONS. |
| |
| NEW COMMENTS |
| |
| 23)2-29-08 COMPLIED. EXCEPTION TO 302.3.2 FOR FIRE |
| SPRINKLERS 1 HR REDUCTION BUT NOT LESS THAN 1 HR.OK |
| |
| 24) SHOWER STALLS- 11-4.23.2 DOORS SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE REQUIRED FOR FIXTURES. THE MAIN |
| DOOR TO THE RESTROOM OVERLAYS THE CLEAR FLOOR SPACE |
| REQUIRED FORTHE SHOWER. |
| |
| 25) 11-4.13.7 DOORS IN SERIES PLEASE REVIEW THE |
| RESTROOM ENTRY DOOR AND THE ACCESSIBLE STALL DOOR. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |