Plan Review Notes
Plan Review Notes For Permit 07080406
Permit Number 07080406
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-27 16:26:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH DALIMA STUDIO TITLE BLOCK. THE FIRMS
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055. PLEASE INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCK ON EACH SHEET.
  
 2. SHT A200. THE A-3 OCCUPANCY REQUIRES A DRINKING
 FOUNTAIN, BUT A BOTTLED WATER COOLER IS SHOWN. THIS IS
 NOT APPROVED. BOTTLED WATER DISPENSERS SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF
 THE REQUIRED DRINKING FOUNTAINS. SINCE ONLY ONE
 DRINKING FOUNTAIN IS REQUIRED, THE BOTTLED WATER
 DISPENSER IS BEING SUBSTITUTED FOR 100% OF THE REQUIRED
 FIXTURES. TABLE 403.1 AND SECTION 410.1. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE
 ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE
 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC
 OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH
 WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES
 TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE
 TOILET AND LAV IN THE STALL/COMPARTMENT.
  
 5. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV
 FOR THE W/C OUTSIDE THE ACCESSIBLE STALL. SECTION
 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE
 THE ACCESSIBLE STALL.
  
 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND
 SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH
 WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL
 OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS
 AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY.
 SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN
 THE STALL/COMPARTMENT.
  
 7. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV
 FOR THE URINAL OUTSIDE THE ACCESSIBLE STALL. SECTION
 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE
 THE ACCESSIBLE STALL.
  
 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 ___URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___ FOR LAVS
 A. 11-4.19.5 FAUCETS
 ___SHOWERS
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEATS
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 C. 11-4.21.6 SHOWER UNITS
 E. 11-4.21.7 CURBS
 PLEASE SUBMIT DETAILS OR ELEVATIONS AND ADJUST DETAILS
 ALREADY SUBMITTED. SEE SECTION 11-4.23AND ALL
 SUBSECTIONS.
  
 9. SHT P-1 DETAIL 1 THE SHOWER IN BATHROOM #2. PER
 TABLE 906.1 THE MAXIMUM DISTANCE FROM THE TRAP TO THE
 VENT FOR 2" IS 6FT. PER THE FLOOR PLAN, THIS SCALES OUT
 TO 8FT. PLEASE CHECK DISTANCE FROM TRAP TO VENT FOR THE
 SHOWER.
  
 10. SHT P-1 DETAIL 1 APPLIANCE P-6 IS NOT INDICATED ON
 THE PLUMBING FIXTURE SCHEDULE FOUND ON SHT P-3. PLEASE
 INDICATE WHAT TYPE OF FIXTURE THIS IS. SECTION
 106.1.1.
  
 11. SHT P-1 DETAIL 1 BATHROOM 3 IS INDICATED AS CLOSET
 NO.3. PLEASE CLARIFY. (ALSO SEE OTHER SHEETS). SECTION
 106.1.1.
  
 12. SHT P-2 SANITARY RISER DIAGRAM. ITEM P-6. IF THE
 ITEM IS A WASH MACHINE, THEN 3" IS REQUIRED FOR THE
 BRANCH DRAIN AND STACK SECTION 406.3--ALSO A
 STANDPIPE IS REQUIRED FOR THE W/M PER SECTIONS 1002.1 &
 802.4.--A CLEANOUT SHALL BE INSTALLED AT LEAST 4FT
 ABOVE THE FLOOR PER SECTION 708.9. PLEASE SHOW ON THE
 ISOMETRIC IF P-6 IS THE WASH MACHINE.
  
 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL
 OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE
 RISER DIAGRAM.
  
 14. SHT P-3 PLEASE SUBMIT THE CALCULATIONS FOR THE
 EXPANSION TANK. PLEASE SUBMIT THE MANUF. SPECIFICATION
 SHEETS FOR THE EXPANSION TANK AND INDICATE THE MODEL
 NUMBER. SECTION 607.3.2.
  
 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT
 DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT
 INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3
 INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V.
 PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO
 INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL
 WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL
 CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL
 SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION
 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved