Date |
Text |
2007-09-27 16:26:37 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL SHEETS WITH DALIMA STUDIO TITLE BLOCK. THE FIRMS |
| LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS |
| REQUIRED ON EACH SHEET. FAC 61G1-16.004(2) & FS |
| 481.219, 481.2055. PLEASE INDICATE FIRM LICENSE NUMBER |
| IN THE TITLE BLOCK ON EACH SHEET. |
| |
| 2. SHT A200. THE A-3 OCCUPANCY REQUIRES A DRINKING |
| FOUNTAIN, BUT A BOTTLED WATER COOLER IS SHOWN. THIS IS |
| NOT APPROVED. BOTTLED WATER DISPENSERS SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF |
| THE REQUIRED DRINKING FOUNTAINS. SINCE ONLY ONE |
| DRINKING FOUNTAIN IS REQUIRED, THE BOTTLED WATER |
| DISPENSER IS BEING SUBSTITUTED FOR 100% OF THE REQUIRED |
| FIXTURES. TABLE 403.1 AND SECTION 410.1. PLEASE |
| INDICATE THE LOCATION OF THE DRINKING FOUNTAIN. |
| |
| 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS |
| WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| |
| 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE |
| ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE |
| 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC |
| OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH |
| WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES |
| TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE |
| TOILET AND LAV IN THE STALL/COMPARTMENT. |
| |
| 5. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV |
| FOR THE W/C OUTSIDE THE ACCESSIBLE STALL. SECTION |
| 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE |
| THE ACCESSIBLE STALL. |
| |
| 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND |
| SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH |
| WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS |
| AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. |
| SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN |
| THE STALL/COMPARTMENT. |
| |
| 7. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV |
| FOR THE URINAL OUTSIDE THE ACCESSIBLE STALL. SECTION |
| 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE |
| THE ACCESSIBLE STALL. |
| |
| 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| ___W/C'S |
| A. 11-4.16.5 FLUSH CONTROLS |
| ___URINAL |
| A. 11-4.18.2 HEIGHT |
| B. 11-4.18.3 CLEAR FLOOR SPACE |
| C. 11-4.18.4 FLUSH CONTROLS |
| ___ FOR LAVS |
| A. 11-4.19.5 FAUCETS |
| ___SHOWERS |
| A. 11-4.21.2 SIZE & CLEARANCES |
| B. 11-4.21.3 SEATS |
| C. 11-4.21.4 GRAB BARS |
| D. 11-4.21.5 CONTROLS |
| C. 11-4.21.6 SHOWER UNITS |
| E. 11-4.21.7 CURBS |
| PLEASE SUBMIT DETAILS OR ELEVATIONS AND ADJUST DETAILS |
| ALREADY SUBMITTED. SEE SECTION 11-4.23AND ALL |
| SUBSECTIONS. |
| |
| 9. SHT P-1 DETAIL 1 THE SHOWER IN BATHROOM #2. PER |
| TABLE 906.1 THE MAXIMUM DISTANCE FROM THE TRAP TO THE |
| VENT FOR 2" IS 6FT. PER THE FLOOR PLAN, THIS SCALES OUT |
| TO 8FT. PLEASE CHECK DISTANCE FROM TRAP TO VENT FOR THE |
| SHOWER. |
| |
| 10. SHT P-1 DETAIL 1 APPLIANCE P-6 IS NOT INDICATED ON |
| THE PLUMBING FIXTURE SCHEDULE FOUND ON SHT P-3. PLEASE |
| INDICATE WHAT TYPE OF FIXTURE THIS IS. SECTION |
| 106.1.1. |
| |
| 11. SHT P-1 DETAIL 1 BATHROOM 3 IS INDICATED AS CLOSET |
| NO.3. PLEASE CLARIFY. (ALSO SEE OTHER SHEETS). SECTION |
| 106.1.1. |
| |
| 12. SHT P-2 SANITARY RISER DIAGRAM. ITEM P-6. IF THE |
| ITEM IS A WASH MACHINE, THEN 3" IS REQUIRED FOR THE |
| BRANCH DRAIN AND STACK SECTION 406.3--ALSO A |
| STANDPIPE IS REQUIRED FOR THE W/M PER SECTIONS 1002.1 & |
| 802.4.--A CLEANOUT SHALL BE INSTALLED AT LEAST 4FT |
| ABOVE THE FLOOR PER SECTION 708.9. PLEASE SHOW ON THE |
| ISOMETRIC IF P-6 IS THE WASH MACHINE. |
| |
| 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS |
| REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL |
| OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE |
| RISER DIAGRAM. |
| |
| 14. SHT P-3 PLEASE SUBMIT THE CALCULATIONS FOR THE |
| EXPANSION TANK. PLEASE SUBMIT THE MANUF. SPECIFICATION |
| SHEETS FOR THE EXPANSION TANK AND INDICATE THE MODEL |
| NUMBER. SECTION 607.3.2. |
| |
| 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT |
| DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT |
| INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 |
| INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. |
| PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO |
| INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL |
| WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL |
| CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL |
| SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION |
| 13-103. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |