Plan Review Notes
Plan Review Notes For Permit 07080406
Permit Number 07080406
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-18 15:48:53REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGNER OR OWNER MUST SELECT THE LEVEL OF
 ALTERATION BEING PROPOSED PER FBC,EB 301.5.
  
 2. IS THIS A CHANGE OF OCCUPANCY? SEE FBC,EB 301.4 AND
 306.1.
  
 3. VALUE OF WORK HAS NOT BEEN DECLARED. FOR PURPOSE OF
 FBC CH,13 COMPLIANCE, IT IS ASSUMED THAT THE WORK
 QUALIFIES AS A RENOVATION AS DEFINED IN FBC 13-202.
  
 4. AC-1: LOCATION OF CU-2 APPEARS TO BE IN CONFLICT
 WITH STAIR LANDING ON WEST ELEVATION. VERIFY REQUIRED
 CLEARANCES FOR CU PER FBC,M 304.1.
  
 5. AC-1: BATH AND DRYER EXHAUST FROM RESIDENCE WILL BE
 DISCHARGING ONTO THE STAIR SHOWN ON WEST ELEVATION.
 EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS PER
 FBC,M 401.5.2.
  
 6. AC-1: REFRIGERANT LINES FOR CU-2/AHU-2, IF THEY ARE
 TO RUN ABOVE CEILING, THEY MAY BE IN CONFLICT WITJ
 STAIR ON WEST ELEVATION WHEN THEY LEAVE THE BUILDING.
 PLEASE VERIFY THERE IS NO CONFLICT. FBC 106.1.2.
  
 7. PG LSP200 SHOWS AHU IN CLOSET ON 2ND FL NEXT TO
 JANITOR'S CLOSET. PG AC-1 DOES NOT. PLEASE COORDINATE
 PLANS. FBC 106.1.1 AND 106.1.3.
  
 8. AC-1: PLEASE PROVIDE CALCULATIONS SHOWING HOW THE
 VENTILATION REQUIREMENTS OF FRC 303.1 ARE BEING MET FOR
 THE RESIDENCE.
  
 9. AC-1: ALL A/C CLOSETS SHALL BE LINED WITH A
 CONTINUOUS, NON-POPOUS, APPROVED AIR BARRIER AND
 EXTERIOR WALLS USED AS A PLENUM SHALL BE INSULATED TO
 MIN. R-8 PER FBC,M 603.8 AND 603.9.
  
 10. PG AC-1: CONDENSER MOUNTING DETAIL, FBC,M 301.13.1
 ONLY APPLIES TO R-3 OCCUPANCIES AND 5 TONS OR LESS. THE
 PRESCRIPTIVE METHOD OF 301.13.1 ONLY APPLIES TO CU-2.
 PROVIDE ENGINEERING FOR WIND LOADS AND ATTACHMNENTS FOR
 OTHER CU'S PER FBC,M 301.13 AND FBC CH.16.
  
 11. AC-1: NOTE #14, CONDENSATE DRAIN LINES SHALL BE OF
 NON COMBUSTIBLE MATERIALS PER FBC,M 602.2.1.
  
 12. AC-1: PROVIDE DETAIL AND LISTING OF
 THROUGH-PENETRATION FIRESTOP SYSTEM FOR LINES
 PENETRATING THE RATED STORAGE ROOM PER FBC 712.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  