2007-09-18 15:48:53 | REVIEW #: 1 |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. THE DESIGNER OR OWNER MUST SELECT THE LEVEL OF |
| ALTERATION BEING PROPOSED PER FBC,EB 301.5. |
| |
| 2. IS THIS A CHANGE OF OCCUPANCY? SEE FBC,EB 301.4 AND |
| 306.1. |
| |
| 3. VALUE OF WORK HAS NOT BEEN DECLARED. FOR PURPOSE OF |
| FBC CH,13 COMPLIANCE, IT IS ASSUMED THAT THE WORK |
| QUALIFIES AS A RENOVATION AS DEFINED IN FBC 13-202. |
| |
| 4. AC-1: LOCATION OF CU-2 APPEARS TO BE IN CONFLICT |
| WITH STAIR LANDING ON WEST ELEVATION. VERIFY REQUIRED |
| CLEARANCES FOR CU PER FBC,M 304.1. |
| |
| 5. AC-1: BATH AND DRYER EXHAUST FROM RESIDENCE WILL BE |
| DISCHARGING ONTO THE STAIR SHOWN ON WEST ELEVATION. |
| EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS PER |
| FBC,M 401.5.2. |
| |
| 6. AC-1: REFRIGERANT LINES FOR CU-2/AHU-2, IF THEY ARE |
| TO RUN ABOVE CEILING, THEY MAY BE IN CONFLICT WITJ |
| STAIR ON WEST ELEVATION WHEN THEY LEAVE THE BUILDING. |
| PLEASE VERIFY THERE IS NO CONFLICT. FBC 106.1.2. |
| |
| 7. PG LSP200 SHOWS AHU IN CLOSET ON 2ND FL NEXT TO |
| JANITOR'S CLOSET. PG AC-1 DOES NOT. PLEASE COORDINATE |
| PLANS. FBC 106.1.1 AND 106.1.3. |
| |
| 8. AC-1: PLEASE PROVIDE CALCULATIONS SHOWING HOW THE |
| VENTILATION REQUIREMENTS OF FRC 303.1 ARE BEING MET FOR |
| THE RESIDENCE. |
| |
| 9. AC-1: ALL A/C CLOSETS SHALL BE LINED WITH A |
| CONTINUOUS, NON-POPOUS, APPROVED AIR BARRIER AND |
| EXTERIOR WALLS USED AS A PLENUM SHALL BE INSULATED TO |
| MIN. R-8 PER FBC,M 603.8 AND 603.9. |
| |
| 10. PG AC-1: CONDENSER MOUNTING DETAIL, FBC,M 301.13.1 |
| ONLY APPLIES TO R-3 OCCUPANCIES AND 5 TONS OR LESS. THE |
| PRESCRIPTIVE METHOD OF 301.13.1 ONLY APPLIES TO CU-2. |
| PROVIDE ENGINEERING FOR WIND LOADS AND ATTACHMNENTS FOR |
| OTHER CU'S PER FBC,M 301.13 AND FBC CH.16. |
| |
| 11. AC-1: NOTE #14, CONDENSATE DRAIN LINES SHALL BE OF |
| NON COMBUSTIBLE MATERIALS PER FBC,M 602.2.1. |
| |
| 12. AC-1: PROVIDE DETAIL AND LISTING OF |
| THROUGH-PENETRATION FIRESTOP SYSTEM FOR LINES |
| PENETRATING THE RATED STORAGE ROOM PER FBC 712.3. |
| |