2007-10-22 15:19:32 | *****DENIED***** |
| |
| |
| 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED.I.E. ON SHEET LSP200 LISTS 2004 |
| |
| 02.POST/SHOW THE NUMERICAL ADDRESS OF THE BUILDING ON |
| THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SPRUCE |
| AVENUE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL |
| BE NO LESS THAN SIX INCHES IN HEIGHT AND NO LESS THAN |
| ONE INCH IN WIDTH. |
| |
| 03.OUTSIDE STAIRS AND LANDINGS SHALL BE OF SLIP |
| RESISTANT SURFACES AND DESIGNED TO MINIMIZE WATER |
| ACCUMULATION ON THEIR SURFACES. |
| |
| 04.THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME |
| A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| |
| 05.BUILDING ELEMENTS SHALL BE USED TO RESTRICT WATER |
| EXPOSURE OF ELEVATOR EQUIPMENT. |
| |
| 06.IN REFERENCE TO THE DWELLING UNIT ON SHEET E-1, |
| AMEND ELECTRICAL LEGEND ON SHEET E-3 TO REFLECT SMOKE |
| ALARMS INSTEAD OF SMOKE DETECTORS.SMOKE DETECTORS ARE |
| TIED INTO THE BUILDING FIRE ALARM SYSTEM, WHEREAS SMOKE |
| ALARMS ALERT THE OCCUPANTS OF THE SAID UNIT. |
| |
| 07.IN NEW CONSTRUCTION, WHERE TWO OR MORE SMOKE |
| ALARMS ARE REQUIRED WITHIN A DWELLING UNIT, THEY SHALL |
| BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM SHALL |
| CAUSE THE ALARM IN ALL THE OTHER SMOKE ALARMS TO |
| SOUND. |
| |
| 08.AMEND ON SHEET FA-02 UNDER DUCT DETECTOR, DUCT |
| SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM (AS |
| PER LOCAL CODE). |
| |
| 09. KNOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE |
| DEPARTMENT CONNECTIONS.FOR APPLICATIONS, CONTACT WEST |
| PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. |
| |
| 10.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE |
| REQUIRED ON THE FIRE LINE BAK FLOW DEVICE. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE PLANEACH COMMENT WAS |
| ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |