2007-09-21 13:07:55 | CONSTRUCTION SERVICES DEPARTMENT |
| 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| FLORIDA33401 |
| TEL:561-805-6713FAX: |
| 561-805-6731 |
| |
| JAMES JOHNSTON, PERMIT NO 07080406 |
| BUILDING PLAN EXAMINERII PROJECT MASONIC LODGE |
| E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2027 SPRUCE |
| AVENUE |
| CONTRACTOR WPB HOUSING AUTHORITY |
| DATE SEPTEMBER 19, 2007 |
| |
| |
| STRUCTURALPLANREVIEW |
| |
| |
| |
| FBC 1604.5 IMPORTANCE FACTOR. |
| 1 THE VALUE FOR WIND LOAD IMPORTANCE FACTOR SHALL BE |
| DETERMINED IN ACCORDANCE WITH TABLE 1604.5 . |
| COMMENT -IDENTIFY WIND IMPORTANCE FACTOR SHEET CS100 |
| |
| 2 FBC CHAPTER 3IDENTIFY RESIDENTIAL OCCUPANCYR-3 |
| |
| COMMENT- IDENTIFY OCCUPANCIES ON CS100R-3 AND A-3 |
| |
| 3 FBC1004.1 DESIGN OCCUPANT LOAD. |
| IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER |
| OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL |
| BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER |
| COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH |
| 1004.1.3 . |
| COMMENT-ASSEMBLY -CHAIRS ONLY 116 OCCUPANTS |
| |
| 4 FBC1004.3 POSTING OF OCCUPANT LOAD. |
| EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL |
| HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A |
| CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS |
| DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE |
| OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE |
| MAINTAINED BY THE OWNER OR AUTHORIZED AGENT. |
| COMMENT -IDENTIFY SIGNAGE IN AREA OF OCCUPANT LOAD |
| |
| 5. 1.3.3 LOCATION OF ROOF INSULATION. |
| THE ROOF INSULATION SHALL NOT BE INSTALLED ON A |
| SUSPENDED CEILING WITH REMOVABLE CEILING PANELS. |
| THIS IS LOCATED IN THE FBC ENERGY REQUIREMENTS.SHEET |
| A-400DETAIL 1-A 400 SUGGEST THIS AS AN OPTION |
| |
| 6. WINDOW SCHEDULE |
| PLEASE NOTE ON SHEET A-500 WINDOW SCHEDULE THE IMPACT |
| WINDOW DESIGNATION VS. THE NON-IMPACT DESIGNATION |
| |
| |
| |
| |
| |
| PRODUCT APPROVALS |
| |
| 7 ROOF SYSTEM PRODUCT APPROVAL |
| COMMENT -HIGHLIGHT THE COMPONENTS TO BE USED IN THIS |
| SYSTEM |
| |
| 8 HURRICANE SHUTTER PRODUCT APPROVAL |
| COMMENT -APPROVAL EXPIRED AUGUST 22, 2007 |
| |
| 9 WINDOW PRODUCT APPROVAL |
| PGT INDUSTRIESALUMINUM FIXED WINDOW |
| COMMENT -APPROVAL WILL EXPIRE OCTOBER 3, 2007 |
| |
| |
| FBCEXISTING CHAPTER 2 ? DEFINITION WORK AREA. |
| THAT PORTION OR PORTIONS OF A BUILDING CONSISTING OF |
| ALL RECONFIGURED ELEMENTS, SYSTEMS OR SPACES AS |
| INDICATED ON THE CONSTRUCTION DOCUMENTS. WORK AREA |
| EXCLUDES OTHER PORTIONS OF THE BUILDING WHERE |
| INCIDENTAL WORK ENTAILED BY THE INTENDED WORK MUST BE |
| PERFORMED AND PORTIONS OF THE BUILDING WHERE WORK NOT |
| INITIALLY INTENDED BY THE OWNER IS SPECIFICALLY |
| REQUIRED BY THIS CODE. |
| |
| 10 FBCEXISTING605.4.3 DOOR CLOSING. |
| IN ANY WORK AREA, ALL DOORS OPENING ONTO AN EXIT |
| PASSAGEWAY AT GRADE OR AN EXIT STAIR SHALL BE |
| SELF-CLOSING OR AUTOMATICALLY CLOSING BY LISTED CLOSING |
| DEVICES. |
| COMMENT ?ND 35,ND 01 |
| |
| 11 FBC EXISTING607.3 NEW STRUCTURAL MEMBERS. |
| NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING |
| CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE |
| FLORIDA BUILDING CODE, BUILDING. |
| COMMENT - THIS INCLUDES ROOF SYSTEM/ELEVATOR SHAFT/ |
| INTERIOR AND EXTERIOR COMPONENTS |
| |
| 12 FBC1604.8.1 GENERAL. |
| ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF |
| WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO |
| RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM |
| THE APPLICATION OF THE PRESCRIBED LOADS. |
| COMMENT - ELEVATOR SHAFT ENCLOSURE |
| |
| |
| 13 SHEETS-200? STRUCTURAL NOTES ? |
| COMMENTS |
| 7-SIDENTIFY SLEEVE ANCHOR EMBEDMENT INTO CONCRETE |
| |
| 10-SIDENTIFY # 4 DOWEL EMBEDMENT INTO CONCRETE. |
| |
| SHEET S-100IDENTIFY TIE BEAM ELEVATIONS ON SCHEDULE |
| |
| |
| FBC EXISTING812.5 ACCESSIBILITY. |
| EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A |
| CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL |
| COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 14 FBC ACCESSIBILITY 11-4.10 ELEVATORS |
| COMMENTPLEASE PROVIDE NOTE ON PLAN ELEVATOR MUST |
| COMPLY WITH THIS SECTION |
| |
| |
| |
| 15 FBC11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. |
| THE FLOOR AREA OF ELEVATOR CARS SHALL PROVIDE SPACE FOR |
| WHEELCHAIR USERS TO ENTER THE CAR, MANEUVER WITHIN |
| REACH OF CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE |
| DOOR OPENING AND INSIDE DIMENSIONS |
| THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE |
| EDGE OF ANY HOIST WAY LANDING SHALL BE NO GREATER THAN |
| 1 1 / 4 INCHES (32 MM). |
| |
| 16 ELEVATOR PIT |
| COMMENTIDENTIFY THE DEPTH OF THE PIT FROM FINISHED |
| FLOOR AND ALL OTHER REQUIRED MEASUREMENTS |
| |
| 17 FBC3006.2 VENTING. |
| ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE |
| EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH |
| AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM |
| TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL |
| EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING |
| TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE |
| ELEVATOR EQUIPMENT. |
| COMMENT -WILL THIS SECTION APPLY? |
| |
| |
| 18 FBC1807.3.2 WALLS. ELEVATOR SHAFT WALLS |
| WALLS REQUIRED TO BE WATERPROOFED SHALL BE OF CONCRETE |
| OR MASONRY AND SHALL BE DESIGNED AND CONSTRUCTED TO |
| WITHSTAND THE HYDROSTATIC PRESSURES AND OTHER LATERAL |
| LOADS TO WHICH THE WALLS WILL BE SUBJECTED. |
| COMMENTTHE WALLS OF THE ELEVATOR PIT ARE SUBJECT TO |
| GROUND WATER/MOISTURE INTRUSION. PLEASE DEFINE A |
| WATERPROOFING SYSTEM (NEGATIVE SIDE) OR IF NOT |
| REQUIRED, A SOIL TEST REPORT ON THE GROUND WATER |
| CONDITION |
| |
| |
| FBCRESIDENTIALENERGY CALCULATIONS13-6 |
| |
| PERFORMANCE METHOD ABASE / AS-BUILT |
| |
| 19 GLASS TYPES |
| EAST WALLAREA WITHOUT DEDUCTING FRAME 52.17 S.F. |
| YOUR CALCULATIONS WITH FRAME DEDUCTION 38.5 S.F. |
| PLEASE EXPLAINTHIS. |
| |
| 20 DOOR TYPES |
| EXTERIOR DOOR STEEL.YOUR CALCULATIONS BASED ON WOOD. |
| PLEASE EXPLAIN THIS |
| |
| 21 CEILING TYPES |
| AREA UNDER ATTIC HAS NO INSULATION. THERE IS A |
| CONDITIONED SECOND FLOOR ABOVE THIS RESIDENCE.YOUR |
| CALCULATIONS STATE R 19. PLEASE EXPLAIN THIS. |
| |
| |
| FBCENERGY CALCULATIONS13-6METHOD A WHOLE |
| BUILDING PERFORMANCE |
| |
| SIGNATURE PAGE 3 |
| 22 SIGNATURES ARE MISSING FOR THE ARCHITECT AND |
| ELECTRICAL DESIGNER |