Plan Review Notes
Plan Review Notes For Permit 07080406
Permit Number 07080406
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-21 13:07:55CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07080406
 BUILDING PLAN EXAMINERII PROJECT MASONIC LODGE
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2027 SPRUCE
 AVENUE
  CONTRACTOR WPB HOUSING AUTHORITY
  DATE SEPTEMBER 19, 2007
  
  
 STRUCTURALPLANREVIEW
  
  
  
  FBC 1604.5 IMPORTANCE FACTOR.
 1 THE VALUE FOR WIND LOAD IMPORTANCE FACTOR SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 1604.5 .
 COMMENT -IDENTIFY WIND IMPORTANCE FACTOR SHEET CS100
  
 2 FBC CHAPTER 3IDENTIFY RESIDENTIAL OCCUPANCYR-3
  
 COMMENT- IDENTIFY OCCUPANCIES ON CS100R-3 AND A-3
  
 3 FBC1004.1 DESIGN OCCUPANT LOAD.
 IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER
 OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL
 BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER
 COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH
 1004.1.3 .
 COMMENT-ASSEMBLY -CHAIRS ONLY 116 OCCUPANTS
  
 4 FBC1004.3 POSTING OF OCCUPANT LOAD.
 EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL
 HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR AUTHORIZED AGENT.
 COMMENT -IDENTIFY SIGNAGE IN AREA OF OCCUPANT LOAD
  
 5. 1.3.3 LOCATION OF ROOF INSULATION.
 THE ROOF INSULATION SHALL NOT BE INSTALLED ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
 THIS IS LOCATED IN THE FBC ENERGY REQUIREMENTS.SHEET
 A-400DETAIL 1-A 400 SUGGEST THIS AS AN OPTION
  
 6. WINDOW SCHEDULE
 PLEASE NOTE ON SHEET A-500 WINDOW SCHEDULE THE IMPACT
 WINDOW DESIGNATION VS. THE NON-IMPACT DESIGNATION
  
  
  
  
  
 PRODUCT APPROVALS
  
 7 ROOF SYSTEM PRODUCT APPROVAL
 COMMENT -HIGHLIGHT THE COMPONENTS TO BE USED IN THIS
 SYSTEM
  
 8 HURRICANE SHUTTER PRODUCT APPROVAL
 COMMENT -APPROVAL EXPIRED AUGUST 22, 2007
  
 9 WINDOW PRODUCT APPROVAL
 PGT INDUSTRIESALUMINUM FIXED WINDOW
 COMMENT -APPROVAL WILL EXPIRE OCTOBER 3, 2007
  
  
 FBCEXISTING CHAPTER 2 ? DEFINITION WORK AREA.
 THAT PORTION OR PORTIONS OF A BUILDING CONSISTING OF
 ALL RECONFIGURED ELEMENTS, SYSTEMS OR SPACES AS
 INDICATED ON THE CONSTRUCTION DOCUMENTS. WORK AREA
 EXCLUDES OTHER PORTIONS OF THE BUILDING WHERE
 INCIDENTAL WORK ENTAILED BY THE INTENDED WORK MUST BE
 PERFORMED AND PORTIONS OF THE BUILDING WHERE WORK NOT
 INITIALLY INTENDED BY THE OWNER IS SPECIFICALLY
 REQUIRED BY THIS CODE.
  
 10 FBCEXISTING605.4.3 DOOR CLOSING.
 IN ANY WORK AREA, ALL DOORS OPENING ONTO AN EXIT
 PASSAGEWAY AT GRADE OR AN EXIT STAIR SHALL BE
 SELF-CLOSING OR AUTOMATICALLY CLOSING BY LISTED CLOSING
 DEVICES.
 COMMENT ?ND 35,ND 01
  
 11 FBC EXISTING607.3 NEW STRUCTURAL MEMBERS.
 NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING
 CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 COMMENT - THIS INCLUDES ROOF SYSTEM/ELEVATOR SHAFT/
 INTERIOR AND EXTERIOR COMPONENTS
  
 12 FBC1604.8.1 GENERAL.
 ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF
 WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO
 RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM
 THE APPLICATION OF THE PRESCRIBED LOADS.
 COMMENT - ELEVATOR SHAFT ENCLOSURE
  
  
 13 SHEETS-200? STRUCTURAL NOTES ?
 COMMENTS
 7-SIDENTIFY SLEEVE ANCHOR EMBEDMENT INTO CONCRETE
  
 10-SIDENTIFY # 4 DOWEL EMBEDMENT INTO CONCRETE.
  
 SHEET S-100IDENTIFY TIE BEAM ELEVATIONS ON SCHEDULE
  
  
 FBC EXISTING812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 14 FBC ACCESSIBILITY 11-4.10 ELEVATORS
 COMMENTPLEASE PROVIDE NOTE ON PLAN ELEVATOR MUST
 COMPLY WITH THIS SECTION
  
  
  
 15 FBC11-4.10.9 FLOOR PLAN OF ELEVATOR CARS.
 THE FLOOR AREA OF ELEVATOR CARS SHALL PROVIDE SPACE FOR
 WHEELCHAIR USERS TO ENTER THE CAR, MANEUVER WITHIN
 REACH OF CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE
 DOOR OPENING AND INSIDE DIMENSIONS
 THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE
 EDGE OF ANY HOIST WAY LANDING SHALL BE NO GREATER THAN
 1 1 / 4 INCHES (32 MM).
  
 16 ELEVATOR PIT
 COMMENTIDENTIFY THE DEPTH OF THE PIT FROM FINISHED
 FLOOR AND ALL OTHER REQUIRED MEASUREMENTS
  
 17 FBC3006.2 VENTING.
 ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE
 EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH
 AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM
 TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL
 EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING
 TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE
 ELEVATOR EQUIPMENT.
 COMMENT -WILL THIS SECTION APPLY?
  
  
 18 FBC1807.3.2 WALLS. ELEVATOR SHAFT WALLS
 WALLS REQUIRED TO BE WATERPROOFED SHALL BE OF CONCRETE
 OR MASONRY AND SHALL BE DESIGNED AND CONSTRUCTED TO
 WITHSTAND THE HYDROSTATIC PRESSURES AND OTHER LATERAL
 LOADS TO WHICH THE WALLS WILL BE SUBJECTED.
 COMMENTTHE WALLS OF THE ELEVATOR PIT ARE SUBJECT TO
 GROUND WATER/MOISTURE INTRUSION. PLEASE DEFINE A
 WATERPROOFING SYSTEM (NEGATIVE SIDE) OR IF NOT
 REQUIRED, A SOIL TEST REPORT ON THE GROUND WATER
 CONDITION
  
  
 FBCRESIDENTIALENERGY CALCULATIONS13-6
  
 PERFORMANCE METHOD ABASE / AS-BUILT
  
 19 GLASS TYPES
 EAST WALLAREA WITHOUT DEDUCTING FRAME 52.17 S.F.
 YOUR CALCULATIONS WITH FRAME DEDUCTION 38.5 S.F.
 PLEASE EXPLAINTHIS.
  
 20 DOOR TYPES
 EXTERIOR DOOR STEEL.YOUR CALCULATIONS BASED ON WOOD.
 PLEASE EXPLAIN THIS
  
 21 CEILING TYPES
 AREA UNDER ATTIC HAS NO INSULATION. THERE IS A
 CONDITIONED SECOND FLOOR ABOVE THIS RESIDENCE.YOUR
 CALCULATIONS STATE R 19. PLEASE EXPLAIN THIS.
  
  
 FBCENERGY CALCULATIONS13-6METHOD A WHOLE
 BUILDING PERFORMANCE
  
 SIGNATURE PAGE 3
 22 SIGNATURES ARE MISSING FOR THE ARCHITECT AND
 ELECTRICAL DESIGNER