 1) NOTE: PLANS, SHEET A-1 MENTIONS TO PROVIDE NEW
 ELECTRICAL SWITCH, YET NO INFORMATION WAS PROVIDED FOR
 THIS DEVICE(S).
 PLEASE SEE FBC 13-415.1.ABC.1.1, 13-101 AS A NEW
 AUTOMATED DEVICE OF SOME KIND WILL BE REQUIRED.
 PLEASE PROVIDE AND SHOW THE LOCATION OF THE NEW DEVICE
 OR DEVICES DEPENDING ON THE TYPE OF DEVICE AND COVERAGE
 FOR CONTROLS.
 PLEASE PROVIDE THE MAXIMUM TIME(S) FOR DEVICE(S).
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR CIRCUITING OF
 WHAT IS BEING CALLED EXISTING EXIT AND EMERGENCY LIGHTS
 PER 700.12F OF THE 2005 NEC>
  
 3) NOTE: PLEASE STATE THE FOLLOWING CODES ON PLANS.
 2005 NFPA-70 (NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 4) NOTE: IF SPACE AND PR BUILDING CONTAINS A FA SYSTEM,
 PLEASE LOCATE THE NEW OR EXISTING HORNS/STROBE DEVICES
 FOR MINIMUM ADA REQUIREMENTS PER FBC 11-4.28.1,.2 AND
 .3(4).
 IF INSTALLATION ANY NEW DEVICES, OR RELOCATING THE
 MINIMUM LEVELS FOR DEVICES NEED TO MEET THE ADA
 STANDARDS AS STATED IN THE SECTION OF THE CODE ABOVE.
  
 ** THE SCOPE OF WORK IN MINOR IN NATURE AND THERE ARE
 ONLY A FEW ITEMS NEEDED ON PLANS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved