Date |
Text |
2007-08-28 07:26:16 | |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLANS, SHEET A-1 MENTIONS TO PROVIDE NEW |
| ELECTRICAL SWITCH, YET NO INFORMATION WAS PROVIDED FOR |
| THIS DEVICE(S). |
| PLEASE SEE FBC 13-415.1.ABC.1.1, 13-101 AS A NEW |
| AUTOMATED DEVICE OF SOME KIND WILL BE REQUIRED. |
| PLEASE PROVIDE AND SHOW THE LOCATION OF THE NEW DEVICE |
| OR DEVICES DEPENDING ON THE TYPE OF DEVICE AND COVERAGE |
| FOR CONTROLS. |
| PLEASE PROVIDE THE MAXIMUM TIME(S) FOR DEVICE(S). |
| |
| 2) NOTE: PLEASE PROVIDE INFORMATION FOR CIRCUITING OF |
| WHAT IS BEING CALLED EXISTING EXIT AND EMERGENCY LIGHTS |
| PER 700.12F OF THE 2005 NEC> |
| |
| 3) NOTE: PLEASE STATE THE FOLLOWING CODES ON PLANS. |
| 2005 NFPA-70 (NEC) |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 4) NOTE: IF SPACE AND PR BUILDING CONTAINS A FA SYSTEM, |
| PLEASE LOCATE THE NEW OR EXISTING HORNS/STROBE DEVICES |
| FOR MINIMUM ADA REQUIREMENTS PER FBC 11-4.28.1,.2 AND |
| .3(4). |
| IF INSTALLATION ANY NEW DEVICES, OR RELOCATING THE |
| MINIMUM LEVELS FOR DEVICES NEED TO MEET THE ADA |
| STANDARDS AS STATED IN THE SECTION OF THE CODE ABOVE. |
| |
| ** THE SCOPE OF WORK IN MINOR IN NATURE AND THERE ARE |
| ONLY A FEW ITEMS NEEDED ON PLANS. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |