2007-08-28 07:37:11 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, 13-101 AS A
 NEW AUTOMATED DEVICE OF SOME KIND WILL BE REQUIRED FOR
 SWITCH LOCATIONS.
 PLEASE PROVIDE AND SHOW THE LOCATION OF THE NEW DEVICE
 OR DEVICES DEPENDING ON THE TYPE OF DEVICE AND COVERAGE
 FOR CONTROLS.
 PLEASE PROVIDE THE MAXIMUM TIME(S) FOR DEVICE(S).
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR CIRCUITING OF
 WHAT IS BEING CALLED EXISTING EXIT AND EMERGENCY LIGHTS
 PER 700.12F OF THE 2005 NEC> ( ONE MISSING CONNECTION
 OF CIRCUIT)
  
 3) NOTE: PLEASE SEE THE OPEN OFFICE AREA WHERE THE
 EMERGENCY LIGHT FIXTURE IS BEING RELOCATED DOES NOT
 SEEM TO BE PLACED IN THE OPEN OFFICE AREA.
 PLEASE SEE THE MINIMUM FT CANDLES FOR EGRESS PER LS 101
 7.8 AND 7.9
 PLEASE MOVE THE FIXTURE AS SHOWN OR PROVIDE AN
 ADDITIONAL FIXTURE.
 FAC 61G15-33.004
  
 4) NOTE: PLEASE PROVIDE THE MAXIMUM LIGHTING POWER
 DENSITIES PER 13-415.2
  
 5) NOTE: PLEASE PROVIDE A PANEL SCHEDULE FOR NEW AND/OR
 EXISTING CIRCUITS.
 408.4.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE STATE THE FOLLOWING CODES ON PLANS.
 2005 NFPA-70 (NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 ** THE SCOPE OF WORK IN MINOR IN NATURE AND THERE ARE
 ONLY A FEW ITEMS NEEDED ON PLANS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  