2007-08-29 07:58:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 2.)SEE OPENING 3.IT APPEARS THAT THE REQUIRED .5
 FACTOR FOR A 2" EDGE DISTANCE WAS APPLIED TO THE
 BOTTOM, BUT IS REQUIRED AT THE TOP.
  
 3.)SPANS SHOULD BE THE BLADE LENGTH.FOR WALL MOUNT
 CONNECTIONS, THE BLADE LENGTH IS ALWAYS LONGER THAN THE
 OPENING HEIGHT.PLEASE REVISE.
  
 4.)THE MASTER PERMIT 06031357 WAS ISSUED WITH A
 PROVISO TO REVISE SHEETS SP2 AND SP3.I MADE THIS
 PROVISO ON 9/29/06 AT PERMIT ISSUANCE, WITH REQUESTS ON
 1/2/07 AND 3/28/07, AS FOLLOWS:
  
 "THIS PERMIT WAS ISSUED WITH A PROVISO TO REVISE SHEETS
 SP2 AND SP3.THE ORIGINAL PLAN, SHEET SP3, WAS
 REDLINED PER AGREEMENT WITH ARCHITECT.RAMP SECTION 3
 IS TO COMPLY WITH FBC11-4.8.4(2), THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72 INCHES OF STRAIGHT AND
 LEVEL CLEARANCE.PLAN STILL SHOWS 60IN."
  
 THE REVISED SHEETS HAVE NOT BEEN SUBMITTED.PLEASE
 SUBMIT AT THIS TIME.
  
  