2007-08-24 11:12:10 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) PLEASE SHOW A FIRE DAMPER DETAIL ON MECHANICAL PLANS | | AS A FIRE DAMPER IS BEING INSTALLED, SEE MECH. 607.2. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-103.1.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|