2007-09-04 09:27:45PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (WPB), FLORIDA ADMINISTRATIVE CODE (FAC), AND
 FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR
 18,439 SENSIBLE BTU'S, MECHANICAL PLANS ARE CALLING FOR
 30,400 SENSIBLE BTU'S. THE MECHANICAL PLANS SENSIBLE
 BTU'S MAY ONLY BE 20% MORE THAN THE COOLING LOAD
 CALCULATIONS, SEE 2001 FBC 13-607.1.ABC.1.1. PLEASE
 CORRECT.
  
 2) PLEASE SUBMIT TWO (2) COPIES OF THE ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  