Plan Review Notes For Permit 07080328 |
Permit Number |
07080328 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-22 09:55:24 | 1. ON PAGE A-1 ILLUMINATED EXIT SIGNS ARE PRESENT BUT | | ON PAGE ON A-2 ONLY ONE EMERGENCY LIGHT AND EXIT SIGN | | IS DISPLAYED. PLEASE ILLUSTRATE ALL EXISTING AND NEW | | EMERGENCY LIGHTS AND EXIT SIGNS. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | SPRINKLER OR FIRE ALARM SYSTEM REMODEL REQUIRED FOR THE | | SECOND FLOOR SPACE. | | | | 3. PLEASE DECLARE ON THE PLANS WHERE PANIC OR FIRE EXIT | | PANIC DOOR HARDWARE IS PRESENT. | | | | 4. PLANS DO NOT DECLARE ANY EXISTING OR NEW FIRE ALARM | | EQUIPMENT ON THE SECOND FLOOR. PLEASE PROVIDE | | INFORMATION. | | | | 5. PLEASE DISPLAY WHERE SEATING IS PROVIDED FOR THE | | HANDICAPPED. | | | | 6. PLEASE ILLUSTRATE ON THE PLANS THE LOCATIONS OF ANY | | PORTABLE FIRE EXTINGUISHING EQUIPMENT. | | | | 7. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO | | COMPLY WITH NFPA 241. | | | | 8. ALL DEBRIS SHALL BE REMOVED FROM SITE DAILY. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | 804-4709 PHONE | | 804-4774 FAX |
|