Plan Review Notes For Permit 07080328
Permit Number 07080328
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-20 12:42:47NOTE ADDED:
  
  
 ADDRESS ON PLANS CALLS FOR 311 CLEMATIS, HOWEVER
 ADDRESS AS APPLIED IS 309 CLEMATIS. PLEASE CORREALTE
 AND ADJUST.
2007-09-20 12:39:48 
 ** DENIED **
  
 1) NOTE: PLEASE INDICATE IF THERE IS GOING TO BE ANY
 ELECTRICAL FOR BAR AREAS. PLANS INDICATE NO ELECTRICAL
 FOR REVIEW.
 PLEASE INDICATE ELECTRICAL, CIRCUITING, PANEL
 SCHEDULES(S) WITH NEW LOADS ADDED TO EXISTING.
 PLEASE SEE 210.8B FOR GFI PROTECTION IF NOT EXISTING.
 408.4, 240.4, 310.16, 220,
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE NOT SIGNED,
 DATED OR SEALED BY THE DESIGN PROFESSIONAL ON EITHER OF
 THE TWO SETS.
 FS 481.221
  
 3) NOTE: PLEASE INDICATE NEW OR EXISTING LIGHTING
 MEETING THE MINIMUM LEVELS FOR LIFE SAFETY.
 PLEASE SEE 7.8.1.3 AND 7.9.2 FOR STAIR AREAS TO CONTAIN
 10FT CANDLES UNDER NORMAL AND IS PERMITTED TO GO DOWN
 TO 1FT CANDLE UNDER EMERGENCY.
 PLEASE ALSO SEE FIRE MARSHAL REVIEW COMMENTS TO
 INDICATE NEW OR EXISTING EXIT AND EMERGENCY LIGHTING.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING.
  
 4) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 EVEN IF ANY OF THESE ARE OWNER SUPPLIED.
 THE VALUE AS APPLIED SEEMS LOW FOR THE SCOPE OF WORK
 SHOWN AND TO BE PERFORMED.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717