2007-09-26 19:40:24 | BUILDING PLAN REVIEW |
| PERMIT: 07080328 |
| ADD: 309 CLEMATIS ST |
| CONT: WELLINGTON EQUESTRIAN DEV |
| TEL: (561)248-3403 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT |
| STATEMENT --- |
| PLEASE DO |
| NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM |
| BEACH ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS ASUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 2) PLANS DRAWN BY ARCHITECT KELLY D YATES NEEDS TO SIGN |
| SEAL AND DATE PLANS. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ATATE |
| STAT: 61G16.003 ARCHITECTS |
| |
| 3) PLEASE VERIFY THE ADDRESS WHERE THE WORK TO BE |
| COMPLETED UNDER THIS PERMIT WILL TAKE PLACE, THE PERMIT |
| APPLICATION INDICATES 309 CLEMATIS ST WHILE THE PLANS |
| INDICATE 311 CLEMATIS ST.ADDITIONAL INFORMATION |
| REQUIRED 106.1.2*. |
| |
| 4) PLEASE UPDATE CODE ANALYSIS TO INCLUDE 2004 FBC |
| BUILDING WITH THE 2007 REVISIONS EFFECTIVE JULY1, |
| 2007. |
| |
| 5) PLEASE UPDATE CODE ANALYSIS TO ALSO INCLUDE THE 2004 |
| EXISTING BUILDING CODE WITH 2006 REVISIONS, TO INDICATE |
| WHAT LEVEL ALTERATIONS TO BE COVERED UNDER THIS PERMIT? |
| ADDITIONAL INFORMATION REQUIRED 106.1.2*. |
| |
| 6) PLEASE INDICATE CODE COMPLIANCE FOR THE FOLLOWING: |
| 6A) 11-4.32.2 SEATING. |
| IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE |
| PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH |
| CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE |
| THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). |
| ALL FIXED SEATING IN PUBLIC FOOD SERVICE |
| ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE |
| BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN |
| ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION |
| 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE |
| WITH THE FOLLOWING REQUIREMENTS: |
| (1)ALL AISLES ADJACENT TO FIXED SEATING SHALL |
| PROVIDE CLEAR FLOOR SPACE FOR WHEELCHAIRS. |
| (2)WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES |
| OF SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 |
| INCHES (1321 MM) WIDE. |
| |
| 11-4.32.3 KNEE CLEARANCES. |
| IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT |
| TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685 |
| MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485 |
| MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 ). |
| |
| 11-4.32.4 HEIGHT OF TABLES OR COUNTERS. |
| THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE |
| FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM) ABOVE |
| THE FINISH FLOOR OR GROUND. |
| |
| 6B)11-4.33.1 MINIMUM NUMBER. |
| ALL PUBLIC FOOD SERVICE ESTABLISHMENTS, ALL |
| ESTABLISHMENTS LICENSED UNDER THE BEVERAGE LAW FOR |
| CONSUMPTION ON THE PREMISES, AND ASSEMBLY AND |
| ASSOCIATED AREAS REQUIRED TO BE ACCESSIBLE BY SECTION |
| 11-4.1 SHALL COMPLY WITH SECTION11-4.33. |
| |
| 11-4.33.2 SIZE OF WHEELCHAIR LOCATIONS. |
| EACH WHEELCHAIR LOCATION SHALL PROVIDE MINIMUM CLEAR |
| GROUND OR FLOOR SPACES AS SHOWN IN FIGURE 46 . |
| |
| |
| 11-4.33.3 PLACEMENT OF WHEELCHAIR LOCATIONS. |
| WHEELCHAIR AREAS SHALL BE AN INTEGRAL PART OF ANY FIXED |
| SEATING PLAN AND SHALL BE PROVIDED SO THEY SHALL ADJOIN |
| AN ACCESSIBLE ROUTE THAT ALSO SERVES AS A MEANS OF |
| EGRESS IN CASE OF EMERGENCY. |
| |
| 6C) 11-5.1GENERAL. |
| EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION, |
| RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE |
| REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 . |
| WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS |
| CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT |
| LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED |
| TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE |
| ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS |
| REQUIRED IN SECTION 11-4.1.3(18). |
| |
| 6D)11-5.2 COUNTERS AND BARS. |
| WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 |
| INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS |
| SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION |
| OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN |
| LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH |
| SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT |
| ACCESSIBLE TABLES WITHIN THE SAME AREA. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| BUILDING PLAN REVIEW |