Plan Review Notes
Plan Review Notes For Permit 07080268
Permit Number 07080268
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-09 16:49:59** DENIED 2ND REVIEW **
  
 ** AS STATED ON PREVIOUS REVIEW, PLEASE SUBMIT
 COMPLETED PLANS FOR MINIMUM NEC COMPLIANCE.
 PLEASE SEE MANY OF THE CODE SECTIONS PREVIOUSLY GIVEN
 ARE NOT ON PLANS.
  
  
 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS
 PREVIOUSLY STATED AND REQUIRED BY FBC.
 2004 FBC/W2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THESE MAY BE SHOWN ALREADY.
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR
 RESIDENTIAL DWELLING. NEC 220
  
 3) NOTE: PLEASE SEE MIN VA FOR WASHER/LAUNDRY CIRCUIT
 SHALL MEET 220.53.
 1500 MIN.
  
 4) NOTE: PLEASE CORRELATE RISER WITH ACTUAL ELECTRICAL
 SERVICE AT LOCATION.
 PLANS INDICATE A METER CENTER AND RISER SHOWS A
 SEPARATE SERVICE WITH METER MAIN COMBO PANEL.
 THESE ARE NOT COORDINATED OR CLEAR.
 230.2
 FBC 106.3.5.4, 106.1.2
  
 5) NOTE: PLANS ARE NOT SIGNED DATED OR SEALED BY THE
 DESIGNER OF RECORD.
 FS471.025
  
 6) NOTE: PLEASE LIST ALL ARC FAULT CIRCUITS PER 210.12
  
 7) NOTE: PLANS MISSING EGRESS LIGHTING AT DOOR. 210.70,
 LS 101 7.8
  
 8) NOTE: PLANS MISSING A/C CU DISCONNECT, GFI ETC.
 PLEASE SEE 210.8A, 210.63, 440.11
  
 PLEASE SUBMIT COMPLETED PLANS.
  
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN
 AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]