2007-11-09 16:49:59 | ** DENIED 2ND REVIEW ** |
| |
| ** AS STATED ON PREVIOUS REVIEW, PLEASE SUBMIT |
| COMPLETED PLANS FOR MINIMUM NEC COMPLIANCE. |
| PLEASE SEE MANY OF THE CODE SECTIONS PREVIOUSLY GIVEN |
| ARE NOT ON PLANS. |
| |
| |
| 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS |
| PREVIOUSLY STATED AND REQUIRED BY FBC. |
| 2004 FBC/W2006 REVISIONS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** SOME OF THESE MAY BE SHOWN ALREADY. |
| |
| 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR |
| RESIDENTIAL DWELLING. NEC 220 |
| |
| 3) NOTE: PLEASE SEE MIN VA FOR WASHER/LAUNDRY CIRCUIT |
| SHALL MEET 220.53. |
| 1500 MIN. |
| |
| 4) NOTE: PLEASE CORRELATE RISER WITH ACTUAL ELECTRICAL |
| SERVICE AT LOCATION. |
| PLANS INDICATE A METER CENTER AND RISER SHOWS A |
| SEPARATE SERVICE WITH METER MAIN COMBO PANEL. |
| THESE ARE NOT COORDINATED OR CLEAR. |
| 230.2 |
| FBC 106.3.5.4, 106.1.2 |
| |
| 5) NOTE: PLANS ARE NOT SIGNED DATED OR SEALED BY THE |
| DESIGNER OF RECORD. |
| FS471.025 |
| |
| 6) NOTE: PLEASE LIST ALL ARC FAULT CIRCUITS PER 210.12 |
| |
| 7) NOTE: PLANS MISSING EGRESS LIGHTING AT DOOR. 210.70, |
| LS 101 7.8 |
| |
| 8) NOTE: PLANS MISSING A/C CU DISCONNECT, GFI ETC. |
| PLEASE SEE 210.8A, 210.63, 440.11 |
| |
| PLEASE SUBMIT COMPLETED PLANS. |
| |
| |
| ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN |
| AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| NOT BE DONE. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |