 ** DENIED **
  
 1) NOTE: PLEASE SEE FBC R313 AS NEW SMOKE ALARM/DICTION
 DEVICES ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS. NFPA-72 11.5.1.1, 11.8.3
  
 2) NOTE: PLEASE INDICATE THE NEW AIC RATING FOR NEW
 MAINS AND SERVICE EQUIPMENT.
 110.9, FBC 106.1.2, 106.1.1
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT AS
 REQUIRED PER 250.110, 250.122, 250.24 ETC.
  
 4) NOTE: PLEASE SEE THE RISER SEEMS TO SHOW ONLY ONE
 SERVICE AND NO INDICATION OF THE EXISTING OTHER MAINS
 ETC.
 THIS IS AN APARTMENT, AS APPLIED AND PLEASE SHOW THE
 BUILDING SERVICE, LOCATION ETC. 230.70,230.71,230.72.
  
 5) NOTE: PLEASE INDICATE THE CIRCUITS WHICH ARE
 REQUIRED TO BE SPECIFIC TO ROOMS ARE AREAS IN WHICH
 THEY FEED.
 PLEASE SHOW THE CIRCUITING ON PLANS AND CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULE.
 408.4, 240.4, 310.16.
 FBC 106.3.5.1.2, 106.3.5.4, 106.1.2, 106.1.1
  
 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE
 AHU IS TOO HIGHFOR THE 5KW HEAT SHOWN.
 PLEASE ADJUST. (30AMP)?
  
 7) NOTE: PLEASE SEE THE MINIMUM LOAD FOR THE WATER
 HEATER IS TO BE SIZED AT 125%.
 422.13
 ADJUST LOAD CALCULATIONS.
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  