2007-08-27 20:28:01 | 2007-08-27 20:28:01 |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE SEE FBC R313 AS NEW SMOKE ALARM/DICTION |
| DEVICES ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING |
| ROOMS. NFPA-72 11.5.1.1, 11.8.3 |
| |
| 2) NOTE: PLEASE INDICATE THE NEW AIC RATING FOR NEW |
| MAINS AND SERVICE EQUIPMENT. |
| 110.9, FBC 106.1.2, 106.1.1 |
| |
| 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT AS |
| REQUIRED PER 250.110, 250.122, 250.24 ETC. |
| |
| 4) NOTE: PLEASE SEE THE RISER SEEMS TO SHOW ONLY ONE |
| SERVICE AND NO INDICATION OF THE EXISTING OTHER MAINS |
| ETC. |
| THIS IS AN APARTMENT, AS APPLIED AND PLEASE SHOW THE |
| BUILDING SERVICE, LOCATION ETC. 230.70,230.71,230.72. |
| |
| 5) NOTE: PLEASE INDICATE THE CIRCUITS WHICH ARE |
| REQUIRED TO BE SPECIFIC TO ROOMS ARE AREAS IN WHICH |
| THEY FEED. |
| PLEASE SHOW THE CIRCUITING ON PLANS AND CORRELATE WITH |
| THE SUBMITTED PANEL SCHEDULE. |
| 408.4, 240.4, 310.16. |
| FBC 106.3.5.1.2, 106.3.5.4, 106.1.2, 106.1.1 |
| |
| 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE |
| AHU IS TOO HIGHFOR THE 5KW HEAT SHOWN. |
| PLEASE ADJUST. (30AMP)? |
| |
| 7) NOTE: PLEASE SEE THE MINIMUM LOAD FOR THE WATER |
| HEATER IS TO BE SIZED AT 125%. |
| 422.13 |
| ADJUST LOAD CALCULATIONS. |
| |
| |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |