2007-09-04 16:54:06 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING W/2006 REV. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE SUBMIT A SEPERATE EXISTING FLOOR PLAN |
| DRAWING INDICATING THE DEMOLITION OF ANY WALLS OR |
| SYSTEMS AND A SEPERATE FLOOR PLAN DRAWING OF THE |
| PROPOSED PROJECT. IF THIS IS AN EXISTING DRYCLEANING |
| BUSSINESS IN OPERATION PLEASE INDICATE THIS ON THE |
| RESUBMITTAL. IF NOT PLEASE STATE THE PREVIOUS OCCUPANCY |
| PER FBC-2004 CHAPTER 1, SECTION 106.1.1, CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED. |
| |
| 2. SHEET P-1 SANITARY RISER DIAGRAM: PER FBC-2004 |
| PLUMBING WITH 2006 REVISIONS TABLE 709.2 THE 3 INCH FS |
| TRAPS ARE INDICATING THE WRONG DRAINAGE FIXTURE UNIT |
| VALUE OF (2 FU) THE CORRECT DRAINAGE FIXTURE UNIT VALUE |
| IS (5 FU) FOR A 3 INCH TRAP. PLEASE REFERENCE THE RED |
| LINE CORRECTIONS OF THIS AND THE UNDERGROUND |
| COMBINATION WASTE AND VENT PIPING. |
| |
| 3. SHEET P-1 SANITARY RISER DIAGRAM IS INDICATING THE |
| FS-1 BOILER ROOM FLOOR DRAIN WITH A 3 INCH TRAP AND |
| SHEET P-2 FIXTURE CONNECTION SCHEDULE IS INDICATING THE |
| FS-1 BOILER ROOM FLOOR DRAIN WITH A 4 INCH TRAP. PLEASE |
| CORRELATE AND CORRECT THIS ON THE RESUBMITTAL PER |
| FBC-2004 CHAPTER 1 SECTION 106.1.1. ALSO IF FS-1 HAS A |
| 4 INCH TRAP PLEASE ADJUST THE (DFU) ACCORDINGLY ON |
| SHEET P-1 SANITARY RISER DIAGRAM. |
| |
| 4. PER FBC-2004 PLUMBING WITH 2006 REVISIONS A |
| DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 AND SHALL |
| BE ADA COMPLIANT PER FBC-2004 CHAPTER 11 THE FOLLOWING |
| SECTIONS: |
| |
| A} 11-4.15, DRINKING FOUNTAINS AND WATER COOLERS |
| ELEVATION DETAIL REQUIRED. |
| |
| B} 11-4.15.2, SPOUT HEIGHT. |
| |
| C} 11-4.15.3, SPOUT LOCATION. |
| |
| D} 11-4.15.4, CONTROLS. |
| |
| E} 11-4.15.5, CLEARENCES (1)(2). |
| |
| F} 11-4.1.3 (10) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN CAAORDANCE TO 11-4.15 AND ONE ACCESSIBLE TO THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS CAN BE |
| ACCOMODATED BY THE USE OF A "HI-LO" FOUNTAIN OR BY SUCH |
| OTHER MEANS AS WOULD ACHIEVE THE REQUIRED ACCESSIBILITY |
| FOR EACH GROUP ON EACH FLOOR). |
| |
| 5. PLEASE PROVIDE INFORMATION THST THE EXISTING |
| RESROOM IS ADA COMPLIANT WITH AN ELEVATION DETAIL PER |
| FBC-2004 CHAPTER 11 THE FOLLOWING SECTIONS: |
| |
| **WATER CLOSETS |
| A} 11-4.16.2, CLEAR FLOOR SPACE. |
| |
| B} 11-4.16.3, HEIGHT. |
| |
| C} 11-4.16.4, GRAB BARS. |
| |
| D} 11-4.16.5, FLUSH CONTROLS. |
| |
| E} 11-4.16.6, DISPENSERS. |
| |
| **LAVATORIES AND MIRRORS |
| A} 11-4.19.2, HEIGHT AND CLEARANCES. |
| |
| B} 11-4.19.3, CLEAR FLOOR SPACE. |
| |
| C} 11-4.19.4, EXPOSED PIPES AND SURFACES. |
| |
| D} 11-4.19.5, FAUCETS. |
| |
| E} 11-4.19.6, MIRRORS. |
| |
| 6. SHEET P-2 EQUIPMENT DRAIN DETAIL: PLEASE INDICATE |
| THE INDIRECT DRAIN LINE REQUIRED AIR GAP PER FBC-2004 |
| PLUMBING WITH 2006 REVISIONS SECTION 802.2.1 THE AIR |
| GAP BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL |
| RIM OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE |
| THE EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE AND |
| CORRELATE THE FIXTURE CONNECTION SCHEDULE (REMARKS) TO |
| REFLECT AIR GAP ON ITEMS 1, 2, 6, 7, 8, 9, 10, 12, 13, |
| 14, 15 AND 16 AS PER THE INDICATED DETAIL INSTEAD OF |
| AIR BREAK. |
| |
| 7. SHEET P-1 AND M-1 ARE INDICATING A GAS FIRED |
| BOILER: PER FBC-2004 PLUMBING WITH 2006 REVISIONS |
| SECTION 701.7,WASTEWATER WHEN DISCHARGED INTO THE |
| BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT |
| HIGHER THAN 140 DEGREES F. WHEN HIGHER TEMPERATURES |
| EXIST, APPROVED COOLING METHODS SHALL BE PROVIDED. ARE |
| THE EQUIPMENT INDIRECT WASTES INTO THE DRAINAGE SYSTEM |
| GOING TO BE GREATER THAN 140 DEGREES F? IF SO, PLEASE |
| CLEARLY INDICATE THIS ON THE RESUBMITTAL IN RELATION TO |
| NOTE 7 ON SHEET P-1 "FOR ALL FLOOR SINKS (FS) THE FIRST |
| TEN FEET OF UNDERGROUND DRAIN PIPING SHALL BE CAST IRON |
| BEFORE TRANSITIONING OVER TO PVC". |
| NOTE: PER FBC-2004 PLUMBING WITH 2006 REVISIONS TABLE |
| 702.2 CPVC IS NOT APPROVED FOR UNDERGROUND BUILDING |
| DRAINAGE. PLEASE DELETE "CPVC" ON THE RESUBMITTAL. |
| |
| 8. SHEET P-1 COMPRESSED AIR GENERAL NOTES: NOTE NUMBER |
| 3, INDICATES SCHEDULE 40. PLEASE CLEARLY INDICATE THE |
| PROPOSED MATERIAL TYPE OF SCHEDULE 40 ON THE |
| RESUBMITTAL. |
| NOTE: PER MANUFACTURER'S SPECIFICATIONS PVC PIPE IS |
| NOT ACCEPTABLE FOR COMPRESSED AIR. |
| |
| 9. SHEET P-2 FIXTURE CONNECTION SCHEDULE ITEM 17, LINT |
| INTERCEPTOR: PLEASE ADD THE FOLLOWING "LINT INTERCEPTOR |
| TO BE INSTALLED PER FBC-2004 PLUMBING WITH 2006 |
| REVISIONS SECTION 1003.6" ON THE RESUBMITTAL. |
| |
| 10. SHEET P-2 GENERAL PLUMBING NOTES: PLEASE DELETE |
| NOTE D.2 "PROVIDE WATER HAMMER ARRESTOR 18" HIGH, NEXT |
| LARGER SIZE THAN PIPE SERVING FIXTURE" (NOTE: WHAT YOU |
| ARE DISCRIBING IS AN AIR CHAMBER, AIR CHAMBERS ARE NO |
| LONGER ALLOWED) AND ADD IN ITS PLACE THE FOLLOWING " |
| PER FBC-2004 PLUMBING WITH 2006 REVISIONS SECTION 604.9 |
| WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE |
| QUICK-CLOSING VALVES ARE UTILIZED. WATER HAMMER |
| ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER'S SPECIFICATIONS. WATER HAMMER ARRESTORS |
| SHALL CONFORM TO ASSE 1010" ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON |
| THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR |
| REFERENCE FOR THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |