2007-09-04 16:54:06DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING W/2006 REV.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT A SEPERATE EXISTING FLOOR PLAN
 DRAWING INDICATING THE DEMOLITION OF ANY WALLS OR
 SYSTEMS AND A SEPERATE FLOOR PLAN DRAWING OF THE
 PROPOSED PROJECT. IF THIS IS AN EXISTING DRYCLEANING
 BUSSINESS IN OPERATION PLEASE INDICATE THIS ON THE
 RESUBMITTAL. IF NOT PLEASE STATE THE PREVIOUS OCCUPANCY
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1, CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED.
  
 2. SHEET P-1 SANITARY RISER DIAGRAM: PER FBC-2004
 PLUMBING WITH 2006 REVISIONS TABLE 709.2 THE 3 INCH FS
 TRAPS ARE INDICATING THE WRONG DRAINAGE FIXTURE UNIT
 VALUE OF (2 FU) THE CORRECT DRAINAGE FIXTURE UNIT VALUE
 IS (5 FU) FOR A 3 INCH TRAP. PLEASE REFERENCE THE RED
 LINE CORRECTIONS OF THIS AND THE UNDERGROUND
 COMBINATION WASTE AND VENT PIPING.
  
 3. SHEET P-1 SANITARY RISER DIAGRAM IS INDICATING THE
 FS-1 BOILER ROOM FLOOR DRAIN WITH A 3 INCH TRAP AND
 SHEET P-2 FIXTURE CONNECTION SCHEDULE IS INDICATING THE
 FS-1 BOILER ROOM FLOOR DRAIN WITH A 4 INCH TRAP. PLEASE
 CORRELATE AND CORRECT THIS ON THE RESUBMITTAL PER
 FBC-2004 CHAPTER 1 SECTION 106.1.1. ALSO IF FS-1 HAS A
 4 INCH TRAP PLEASE ADJUST THE (DFU) ACCORDINGLY ON
 SHEET P-1 SANITARY RISER DIAGRAM.
  
 4. PER FBC-2004 PLUMBING WITH 2006 REVISIONS A
 DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 AND SHALL
 BE ADA COMPLIANT PER FBC-2004 CHAPTER 11 THE FOLLOWING
 SECTIONS:
  
 A} 11-4.15, DRINKING FOUNTAINS AND WATER COOLERS
 ELEVATION DETAIL REQUIRED.
  
 B} 11-4.15.2, SPOUT HEIGHT.
  
 C} 11-4.15.3, SPOUT LOCATION.
  
 D} 11-4.15.4, CONTROLS.
  
 E} 11-4.15.5, CLEARENCES (1)(2).
  
 F} 11-4.1.3 (10) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN CAAORDANCE TO 11-4.15 AND ONE ACCESSIBLE TO THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS CAN BE
 ACCOMODATED BY THE USE OF A "HI-LO" FOUNTAIN OR BY SUCH
 OTHER MEANS AS WOULD ACHIEVE THE REQUIRED ACCESSIBILITY
 FOR EACH GROUP ON EACH FLOOR).
  
 5. PLEASE PROVIDE INFORMATION THST THE EXISTING
 RESROOM IS ADA COMPLIANT WITH AN ELEVATION DETAIL PER
 FBC-2004 CHAPTER 11 THE FOLLOWING SECTIONS:
  
 **WATER CLOSETS
 A} 11-4.16.2, CLEAR FLOOR SPACE.
  
 B} 11-4.16.3, HEIGHT.
  
 C} 11-4.16.4, GRAB BARS.
  
 D} 11-4.16.5, FLUSH CONTROLS.
  
 E} 11-4.16.6, DISPENSERS.
  
 **LAVATORIES AND MIRRORS
 A} 11-4.19.2, HEIGHT AND CLEARANCES.
  
 B} 11-4.19.3, CLEAR FLOOR SPACE.
  
 C} 11-4.19.4, EXPOSED PIPES AND SURFACES.
  
 D} 11-4.19.5, FAUCETS.
  
 E} 11-4.19.6, MIRRORS.
  
 6. SHEET P-2 EQUIPMENT DRAIN DETAIL: PLEASE INDICATE
 THE INDIRECT DRAIN LINE REQUIRED AIR GAP PER FBC-2004
 PLUMBING WITH 2006 REVISIONS SECTION 802.2.1 THE AIR
 GAP BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL
 RIM OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE
 THE EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE AND
 CORRELATE THE FIXTURE CONNECTION SCHEDULE (REMARKS) TO
 REFLECT AIR GAP ON ITEMS 1, 2, 6, 7, 8, 9, 10, 12, 13,
 14, 15 AND 16 AS PER THE INDICATED DETAIL INSTEAD OF
 AIR BREAK.
  
 7. SHEET P-1 AND M-1 ARE INDICATING A GAS FIRED
 BOILER: PER FBC-2004 PLUMBING WITH 2006 REVISIONS
 SECTION 701.7,WASTEWATER WHEN DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT
 HIGHER THAN 140 DEGREES F. WHEN HIGHER TEMPERATURES
 EXIST, APPROVED COOLING METHODS SHALL BE PROVIDED. ARE
 THE EQUIPMENT INDIRECT WASTES INTO THE DRAINAGE SYSTEM
 GOING TO BE GREATER THAN 140 DEGREES F? IF SO, PLEASE
 CLEARLY INDICATE THIS ON THE RESUBMITTAL IN RELATION TO
 NOTE 7 ON SHEET P-1 "FOR ALL FLOOR SINKS (FS) THE FIRST
 TEN FEET OF UNDERGROUND DRAIN PIPING SHALL BE CAST IRON
 BEFORE TRANSITIONING OVER TO PVC".
 NOTE: PER FBC-2004 PLUMBING WITH 2006 REVISIONS TABLE
 702.2 CPVC IS NOT APPROVED FOR UNDERGROUND BUILDING
 DRAINAGE. PLEASE DELETE "CPVC" ON THE RESUBMITTAL.
  
 8. SHEET P-1 COMPRESSED AIR GENERAL NOTES: NOTE NUMBER
 3, INDICATES SCHEDULE 40. PLEASE CLEARLY INDICATE THE
 PROPOSED MATERIAL TYPE OF SCHEDULE 40 ON THE
 RESUBMITTAL.
 NOTE: PER MANUFACTURER'S SPECIFICATIONS PVC PIPE IS
 NOT ACCEPTABLE FOR COMPRESSED AIR.
  
 9. SHEET P-2 FIXTURE CONNECTION SCHEDULE ITEM 17, LINT
 INTERCEPTOR: PLEASE ADD THE FOLLOWING "LINT INTERCEPTOR
 TO BE INSTALLED PER FBC-2004 PLUMBING WITH 2006
 REVISIONS SECTION 1003.6" ON THE RESUBMITTAL.
  
 10. SHEET P-2 GENERAL PLUMBING NOTES: PLEASE DELETE
 NOTE D.2 "PROVIDE WATER HAMMER ARRESTOR 18" HIGH, NEXT
 LARGER SIZE THAN PIPE SERVING FIXTURE" (NOTE: WHAT YOU
 ARE DISCRIBING IS AN AIR CHAMBER, AIR CHAMBERS ARE NO
 LONGER ALLOWED) AND ADD IN ITS PLACE THE FOLLOWING "
 PER FBC-2004 PLUMBING WITH 2006 REVISIONS SECTION 604.9
 WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. WATER HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010" ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  