Plan Review Notes
Plan Review Notes For Permit 07080266
Permit Number 07080266
Review Stop G
Sequence Number 1
Notes
Date Text
2007-09-05 13:43:21DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-1 GAS RISER DIAGRAM: PLEASE CORRELATE THE
 TYPE OF GAS BEING USED. "GAS NOTES" ARE INDICATING A
 NATURAL GAS SIZING TABLE FOR 0.5 PSI AND THE "GAS
 TABLE" IS INDICATING LP SERVICE LOAD AND LP APPLIANCE.
 THIS IS CONFUSING, PLEASE CLEARLY INDICATE THE GAS TYPE
 ON THE RESUBMITTAL. PER FBC-2004 CHAPTER 1 SECTION
 106.1.1, CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF
 THE WORK PROPOSED.
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THERE IS NO CLEAR INDICATION OF THE DELIVERY
 PRESSURE BEING INDICATED ON THE PRINTS OTHER THAN THE
 SIZING TABLE IN THE "GAS NOTES". PLEASE DO THIS ON THE
 RESUBMMITTAL.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 FOR THE DRYER AND THE BOILER WITH THE MANUFACTURER
 NAME, MODEL NUMBER, BTU LOAD, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ON THE
 RESUBMITTAL.
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 5. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  