Date |
Text |
2007-09-05 13:43:21 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SHEET P-1 GAS RISER DIAGRAM: PLEASE CORRELATE THE |
| TYPE OF GAS BEING USED. "GAS NOTES" ARE INDICATING A |
| NATURAL GAS SIZING TABLE FOR 0.5 PSI AND THE "GAS |
| TABLE" IS INDICATING LP SERVICE LOAD AND LP APPLIANCE. |
| THIS IS CONFUSING, PLEASE CLEARLY INDICATE THE GAS TYPE |
| ON THE RESUBMITTAL. PER FBC-2004 CHAPTER 1 SECTION |
| 106.1.1, CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF |
| THE WORK PROPOSED. |
| |
| 2. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| NOTE: THERE IS NO CLEAR INDICATION OF THE DELIVERY |
| PRESSURE BEING INDICATED ON THE PRINTS OTHER THAN THE |
| SIZING TABLE IN THE "GAS NOTES". PLEASE DO THIS ON THE |
| RESUBMMITTAL. |
| |
| 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS |
| FOR THE DRYER AND THE BOILER WITH THE MANUFACTURER |
| NAME, MODEL NUMBER, BTU LOAD, AND A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ON THE |
| RESUBMITTAL. |
| |
| 4. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 5. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 6.6.1. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR |
| REFERENCE FOR THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL= [email protected] |