Plan Review Notes
Plan Review Notes For Permit 07080266
Permit Number 07080266
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-07 14:54:01***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES AND NFPA
 32, WORK SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) PLEASE PROVIDE INFORMATION REGARDING TYPE OF
 SOLVENTS THAT WILL BE USED, AND ANY OTHER HAZARDOUS
 PRODUCTS USED FOR THIS PROCESS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 4) NO SMOKING SIGNS WILL BE REQUIRED TO BE POSTED
 INSIDE THE PLANT.
  
 5) WHAT MEASURES WILL BE TAKEN TO PREVENT THE LEAKING
 OR SPILL OF HAZARDOUS PRODUCTS?
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756