Plan Review Notes
Plan Review Notes For Permit 07080266
Permit Number 07080266
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-06 13:33:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 2} INDICATE PER 230.2 WHY ANOTHER SERVICE AT THIS
 LOCATION IS WARRANTED. ALSO SEE 230.72.
  
 3} INDICATE COMPLIANCE WITH THE APPLICABLE SECTIONS OF
 CHAPTER 13 ENERGY EFFICIENCY, FBC.
  
 4} SEE 306.2 FOR OCCUPANCY CLASSIFICATION OF A DRY
 CLEANER, F-1. CHANGE ON SHEET A1.
  
 5}INDICATE COMPLIANCE WITH NFPA-32, DECLARE PLANT
 TYPE SO THAT ELECTRICAL INSTALLATION CLASS AND DIVISION
 CAN BE DETERMINED.
  
 6} PROVIDE AN EQUIPMENT SCHEDULE FOR EQUIPMENT BEING
 INSTALLED, WITH SPECIFICATIONS AND ELECTRICAL
 REQUIREMENTS.
  
 7} COMPLY WITH NFPA-79 WHERE APPLICABLE.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  