Plan Review Notes
Plan Review Notes For Permit 07080256
Permit Number 07080256
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-05 15:43:42RESIDENTIAL ADDITION BUILDING REVIEW FIRST CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS DOCUMENT MAY BE RECORDED AT A LATER TIME AT
 TIME OF PERMIT PICK UP.
  
 2-ENGINEER TO PROVIDE THE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUE NEEDS TO INCLUDE ALL LABOR,MATERIALS AND
 ENGINEER'S FEES.UPDATE VALUE AS REQUIRED AND INCLUDE
 ALL WORK TO BE PERFORMED OR IT WILL BE UPDATED USING
 THE REFERENCES CITED IN SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 4- SCOPE OF WORK TO BE PERFORMED IS NOT CLEAR.PERMIT
 APPLICATION CALLS FOR COVERED PATIO W/ ELECTRIC, WHILE
 PLANSSHOWNEW ROOF FRAMING FOR ENTIRE HOUSE, PARTIAL
 CARPORT AND NEW COVERED PATIO ADDITION.
 PLANS TO PROVIDE ONLY THE INFORMATION THAT PERTAINS TO
 THE WORK TO BE PERFORMED.DELETE ALL
 DETAILS/SPECIFICATIONS AND NOTESTHAT DON'T APPLY TO
 AVOID CONFUSION OR CONFLICTS. AND, CLEARLY IDENTIFY
 WHAT'S NEW AND WHAT'S EXISTING.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 5- SHEET 2:
 A) LEFT SIDE FLOOR PLANS STATES"EXISTING ROOF
 COVER TO BE REMOVED. RAFTERS & CEILING TO REMAIN".
 THEN, CLARIFY WHY PROVIDING NEW ROOF FRAMING PLAN?
  
 B) MISSINGINFORMATION FOR EXPANSION OF CARPORT.
 NEEDS INFORMATION FOR COLUMNS, BEAMS, RAFTERS, ROOF
 SHEATHING (OR IS THIS A TRELLIS?),FOOTINGS, ETC.
 ALSO, THERE IS A ROOF RAFTER SHOWN AS BEING SUPPORTED
 ON THE AIR. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 C) WINDOW NEXT TO ENTRY DOORAND NEXT TO REAR DOOR
 NEEDS TO HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4
 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY SAFETY
 GLAZING AS REQUIRED.
  
 6- SHEET 5:
 A)NOTE BELOW TRUSS TO CONCRETE SCHEDULE CALLS FOR
 HANGERS TO BE CONCEALED. PROVIDE DETAIL SHOWING HOW ARE
 HANGERS GOING TO BE CONCEALED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) UPDATETRUSS TO TRUSS CONNECTION SCHEDULE AND
 TRUSS TO CONCRETE SCHEDULE. SEE CURRENT CATALOG AND
 SPECIFYFASTENER SIZE , TYPE, NUMBER AND UPLIFTS LOADS
 AS PUBLISHED BY THE MANUFACTURER.OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSISSHOWING WHY VALUES ARE
 DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 7- SHEET 8:
 A) EXISTING TYPICAL WALL SECTION:
 *IT'S NOT CLEAR WHAT'S NEW AND WHAT IS EXISTING.
  
 ** SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF
 2004 FLORIDA RESIDENTIALCODE.
 *** SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806
 OF 2004 FLORIDA RESIDENTIAL CODE.
 **** ROOF TRUSS CONNECTOR SHOWN DOESN'T MATCH TRUSS
 CONNECTORSPECIFIED ON TRUSS CONNECTORSCHEDULE. THIS
 IS A RETROFIT CONNECTOR, NOT AN EMBEDED CONNECTOR.
 REVISE AS REQUIRED.
 ***** REVISE NAIL TYPE AND SPACING TO BE USED FOR ROOF
 SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM NAIL TYPE AND SPACING TO
 BE USED INCLUDING IN ROOF ZONE 3.
  
 B) TYPICAL COLUMN SECTION:
 * THIS SECTION DOESN'T MATCH INFORMATION SHOWN ON DET-1
 ON PAGE 5. REVISE AS REQUIRED TO MATCH.
 ** NUMBER OF REINFORCING BARS SHOWN ON FOOTING DON'T
 MATCH NUMBER OF BARS SPECIFIED ON FOOTING SCHEDULE.
 REVISE AS REQUIRED.
 *** COLUMN SPECIFICATIONS DON'T MATCH SPECIFICATION
 SHOWN ON SHEET 4. REVISE/CLARIFYCOLUMN THICKNESS.
  
 **** IS THERE A NEW OR EXISTING CONCRETE SLAB?.IT'S
 NOT CLEAR WHAT'S NEW AND WHAT'S EXISTING.
 ***** SPECIFY ATTIC VENTILATION. SEC. R806.
 ****** REVISE ROOF SHEATHING NAIL SIZE AND SPACING,
 INCLUDINGROOF ZONE 3. SEC. R803.2.3.1.
 ****** REVISE FINISH CEILING SPECIFICATIONS. THIS IS A
 PATIO CEILING. NEED TO PROVIDE SPECIFICATIONS FOR
 EXTERIOR APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 8- SHEET 9:
 A) REVISE CODE SECTION SPECIFIED ON DESIGN CRITERIA.
 SEE FBC 2004 AND ANDSECTION IS R301 AND TABLE R301.5
 OF 2004 FLORIDA RESIDENTIAL CODE AND SPECIFIED CORRECT
 SECTIONS.
 B) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC.
 602.1 FBC 2004.
 C) REVISE ROOF SHEATHING NAILING SCHEDULE, INCLUDING
 ROOF ZONE 3.SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MIN. NAIL TYPE AND SPACING TO BE
 USED.
 ALSO, REVISE NOTE REGARDING RING SHANK NAILS NOT
 REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25'.
 D)REVISEROOF SHEATHING SPECIFICATIONS SHOWN ON
 PLYWOOD NAILING SKETCH TO MATCH ROOF SHEATHING NAILING
 SCHEDULE, INCLUDING ROOF SHEATHING THICKNESS.
  
 9- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
 B) EXTERIOR DOORS. IF NEW.
 C) WINDOWS.IF NEW.
 D) STORM SHUTTERS IF WINDOWS AND DOORS WITH GLASS
 HAVE NOT IMPACT GLASS.
 ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
 E) PRECAST LINTELS. IF NEW.
 F) ROOF SHINGLES.
 G) FLAT ROOF IF ANY ON CARPORT AREA. AND, CLEARLY
 SPECIFY WHICH SPECIFIC ASSEMBLYAND FASTENING OPTION
 WILL BE INSTALLED. ALSO,PROVIDE RAS 117 CALCULATIONS
 FOR PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION
 #7 ON PRODUCT APPROVAL REPORT.
  
 10 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- IF THERE ARE NEW WINDOWS AND DOORS ,THEN SPECIFY
 TYPE AND SIZES. ALSO, SPECIFY THE DESIGN PRESSURES.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.2 FBC 2004.
 NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
  
 13- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712