2007-09-05 15:43:42 | RESIDENTIAL ADDITION BUILDING REVIEW FIRST CHECKLIST. |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| 2004 WITH 2007 REVISIONS. |
| |
| 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| BY SEC. 713.13 FLORIDA STATUTE. |
| NOTE: THIS DOCUMENT MAY BE RECORDED AT A LATER TIME AT |
| TIME OF PERMIT PICK UP. |
| |
| 2-ENGINEER TO PROVIDE THE FIRM'S CERTIFICATE OF |
| AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| VALUE NEEDS TO INCLUDE ALL LABOR,MATERIALS AND |
| ENGINEER'S FEES.UPDATE VALUE AS REQUIRED AND INCLUDE |
| ALL WORK TO BE PERFORMED OR IT WILL BE UPDATED USING |
| THE REFERENCES CITED IN SEC. 108.3 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 4- SCOPE OF WORK TO BE PERFORMED IS NOT CLEAR.PERMIT |
| APPLICATION CALLS FOR COVERED PATIO W/ ELECTRIC, WHILE |
| PLANSSHOWNEW ROOF FRAMING FOR ENTIRE HOUSE, PARTIAL |
| CARPORT AND NEW COVERED PATIO ADDITION. |
| PLANS TO PROVIDE ONLY THE INFORMATION THAT PERTAINS TO |
| THE WORK TO BE PERFORMED.DELETE ALL |
| DETAILS/SPECIFICATIONS AND NOTESTHAT DON'T APPLY TO |
| AVOID CONFUSION OR CONFLICTS. AND, CLEARLY IDENTIFY |
| WHAT'S NEW AND WHAT'S EXISTING.SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 5- SHEET 2: |
| A) LEFT SIDE FLOOR PLANS STATES"EXISTING ROOF |
| COVER TO BE REMOVED. RAFTERS & CEILING TO REMAIN". |
| THEN, CLARIFY WHY PROVIDING NEW ROOF FRAMING PLAN? |
| |
| B) MISSINGINFORMATION FOR EXPANSION OF CARPORT. |
| NEEDS INFORMATION FOR COLUMNS, BEAMS, RAFTERS, ROOF |
| SHEATHING (OR IS THIS A TRELLIS?),FOOTINGS, ETC. |
| ALSO, THERE IS A ROOF RAFTER SHOWN AS BEING SUPPORTED |
| ON THE AIR. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| C) WINDOW NEXT TO ENTRY DOORAND NEXT TO REAR DOOR |
| NEEDS TO HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4 |
| OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY SAFETY |
| GLAZING AS REQUIRED. |
| |
| 6- SHEET 5: |
| A)NOTE BELOW TRUSS TO CONCRETE SCHEDULE CALLS FOR |
| HANGERS TO BE CONCEALED. PROVIDE DETAIL SHOWING HOW ARE |
| HANGERS GOING TO BE CONCEALED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| B) UPDATETRUSS TO TRUSS CONNECTION SCHEDULE AND |
| TRUSS TO CONCRETE SCHEDULE. SEE CURRENT CATALOG AND |
| SPECIFYFASTENER SIZE , TYPE, NUMBER AND UPLIFTS LOADS |
| AS PUBLISHED BY THE MANUFACTURER.OTHERWISE, PROVIDE |
| COMPLETE ENGINEERING ANALYSISSHOWING WHY VALUES ARE |
| DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| 7- SHEET 8: |
| A) EXISTING TYPICAL WALL SECTION: |
| *IT'S NOT CLEAR WHAT'S NEW AND WHAT IS EXISTING. |
| |
| ** SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF |
| 2004 FLORIDA RESIDENTIALCODE. |
| *** SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806 |
| OF 2004 FLORIDA RESIDENTIAL CODE. |
| **** ROOF TRUSS CONNECTOR SHOWN DOESN'T MATCH TRUSS |
| CONNECTORSPECIFIED ON TRUSS CONNECTORSCHEDULE. THIS |
| IS A RETROFIT CONNECTOR, NOT AN EMBEDED CONNECTOR. |
| REVISE AS REQUIRED. |
| ***** REVISE NAIL TYPE AND SPACING TO BE USED FOR ROOF |
| SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE FOR MINIMUM NAIL TYPE AND SPACING TO |
| BE USED INCLUDING IN ROOF ZONE 3. |
| |
| B) TYPICAL COLUMN SECTION: |
| * THIS SECTION DOESN'T MATCH INFORMATION SHOWN ON DET-1 |
| ON PAGE 5. REVISE AS REQUIRED TO MATCH. |
| ** NUMBER OF REINFORCING BARS SHOWN ON FOOTING DON'T |
| MATCH NUMBER OF BARS SPECIFIED ON FOOTING SCHEDULE. |
| REVISE AS REQUIRED. |
| *** COLUMN SPECIFICATIONS DON'T MATCH SPECIFICATION |
| SHOWN ON SHEET 4. REVISE/CLARIFYCOLUMN THICKNESS. |
| |
| **** IS THERE A NEW OR EXISTING CONCRETE SLAB?.IT'S |
| NOT CLEAR WHAT'S NEW AND WHAT'S EXISTING. |
| ***** SPECIFY ATTIC VENTILATION. SEC. R806. |
| ****** REVISE ROOF SHEATHING NAIL SIZE AND SPACING, |
| INCLUDINGROOF ZONE 3. SEC. R803.2.3.1. |
| ****** REVISE FINISH CEILING SPECIFICATIONS. THIS IS A |
| PATIO CEILING. NEED TO PROVIDE SPECIFICATIONS FOR |
| EXTERIOR APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 8- SHEET 9: |
| A) REVISE CODE SECTION SPECIFIED ON DESIGN CRITERIA. |
| SEE FBC 2004 AND ANDSECTION IS R301 AND TABLE R301.5 |
| OF 2004 FLORIDA RESIDENTIAL CODE AND SPECIFIED CORRECT |
| SECTIONS. |
| B) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. |
| 602.1 FBC 2004. |
| C) REVISE ROOF SHEATHING NAILING SCHEDULE, INCLUDING |
| ROOF ZONE 3.SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE FOR MIN. NAIL TYPE AND SPACING TO BE |
| USED. |
| ALSO, REVISE NOTE REGARDING RING SHANK NAILS NOT |
| REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25'. |
| D)REVISEROOF SHEATHING SPECIFICATIONS SHOWN ON |
| PLYWOOD NAILING SKETCH TO MATCH ROOF SHEATHING NAILING |
| SCHEDULE, INCLUDING ROOF SHEATHING THICKNESS. |
| |
| 9- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS. |
| B) EXTERIOR DOORS. IF NEW. |
| C) WINDOWS.IF NEW. |
| D) STORM SHUTTERS IF WINDOWS AND DOORS WITH GLASS |
| HAVE NOT IMPACT GLASS. |
| ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE. |
| E) PRECAST LINTELS. IF NEW. |
| F) ROOF SHINGLES. |
| G) FLAT ROOF IF ANY ON CARPORT AREA. AND, CLEARLY |
| SPECIFY WHICH SPECIFIC ASSEMBLYAND FASTENING OPTION |
| WILL BE INSTALLED. ALSO,PROVIDE RAS 117 CALCULATIONS |
| FOR PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION |
| #7 ON PRODUCT APPROVAL REPORT. |
| |
| 10 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 11- IF THERE ARE NEW WINDOWS AND DOORS ,THEN SPECIFY |
| TYPE AND SIZES. ALSO, SPECIFY THE DESIGN PRESSURES. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 12- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-600.1.C.2 FBC 2004. |
| NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. |
| |
| 13- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |