2007-09-17 07:39:18 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| FROM PREVIOUS LISTS: |
| |
| 1.)SEE SHEET 14 OF THE PRODUCT APPROVAL.AN EDGE |
| DISTANCE OF 3" REQUIRES A .83 FACTOR. |
| |
| 3RD REVIEW - A NOTE WAS INCLUDED WHICH DISPUTED THE |
| PREVIOUS LISTS.PART OF THE NOTE STATED THAT THE |
| PREVIOUS INSTALLATION SCHEDULE EDGE DISTANCE WAS |
| REVISED TO THE WAY THAT I WANTED IT.PLEASE NOTE THAT |
| EDGE DISTANCE IS DETERMINED BY JOB CONDITIONS AND THE |
| CONTRACTOR.YOU MAY USE ANY CODE COMPLIANT EDGE |
| DISTANCE ON THE PRODUCT APPROVAL (2" AND OVER FOR |
| CONCRETE/BLOCK SUBSTRATES) BUT IF YOU USE A DIMENSION |
| LESS THAN 3 1/2", THEN YOU NEED TO APPLY THE FACTOR AS |
| SHOWN ON PAGE 14.I HAVE DISCUSSED THIS WITH TRACY; |
| PLEASE HAVE HIM CONTACT ME IF YOU NEED FURTHER |
| ASSISTANCE. |
| |
| |
| ***REVISED*** |
| |
| CONTRACTOR INFORMED ME THAT THERE IS A SECOND |
| INSTALLATION SCHEDULE IN THE PACKAGE.THE SECOND ONE |
| HAS A 3" EDGE DISTANCE.THE FACTOR WAS STILL NOT |
| APPLIED ON EITHER INSTALLATION SCHEDULE, BOTH STATE 10" |
| FOR CONNECTION TYPE A.FOR 2" EDGE DISTANCE, THIS |
| SHOULD BE 5" SPACING.FOR 3 1/2" EDGE DISTANCE, THIS |
| SHOULD BE 8.3. |
| |
| THE LETTER INCLUDED STATES THAT TRACY FEELS THAT I WAS |
| INCORRECT IN MY FIRST CORRECTION LIST.I AM RETAINING |
| THE LETTER, BOTH INSTALLATION SCHEDULES, AND THE |
| PRODUCT APPROVAL.I BELIEVE THAT I GOT THIS ISSUE |
| RESOLVED WITH TRACY ON FRIDAY, 9/14, THE DAY AFTER THE |
| LETTER WAS WRITTEN.IF YOU STILL FEEL THAT I AM IN |
| ERROR, PLEASE HAVE TRACY FIRST CONTACT THE TECHNICAL |
| REPRESENTATIVE FOR THE SHUTTERS, AND IF HE AGREES WITH |
| TRACY, PLEASE HAVE HIM CONTACT ME. |
| |