2007-08-31 07:38:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)SEE SHEET 14 OF THE PRODUCT APPROVAL.AN EDGE | | DISTANCE OF 3" REQUIRES A .83 FACTOR. | | | | 2.)SPAN IS GREATER THAN 9'.IF THE OPENING IS 106", | | WALL MOUNT, SPAN SHOULD BE APPROXIMATELY 109" PER | | MANUFACTURER, WHICH IS 9'1" FOR A 3" EDGE DISTANCE TOP | | AND BOTTOM.PLEASE CLARIFY HOW YOU'VE ARRIVED AT THIS | | SPAN BASED ON THE INFORMATION PROVIDED. | | |
|