Plan Review Notes For Permit 07080199 |
Permit Number |
07080199 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-15 11:17:32 | | | | | CLARIFY WHERE THE ENCLOSURE IS TO BE CONSTRUCTED. | | 680.26(B)(5) METAL WIRING METHODS AND EQUIPMENT. | | METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, AND | | ALL FIXED METAL PARTS EXCEPT THOSE SEPARATED FROM THE | | POOL BY A PERMANENT BARRIER SHALL BE BONDED THAT ARE | | WITHIN THE FOLLOWING DISTANCES OF THE POOL: | | EXAMPLES OF FIXED METAL PARTS BOUND BY THIS REQUIREMENT | | INCLUDE METAL FENCES, METAL AWNINGS, METAL DOOR FRAMES, | | AND METAL WINDOW FRAMES. | | (1) WITHIN 1.5 M (5 FT) HORIZONTALLY OF THE INSIDE | | WALLS OF THE POOL | | (2) WITHIN 3.7 M (12 FT) MEASURED VERTICALLY ABOVE THE | | MAXIMUM WATER LEVEL OF THE POOL, OR ANY OBSERVATION | | STANDS, TOWERS, OR PLATFORMS, OR ANY DIVING | | STRUCTURES. | | | | THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | AMENDED. | | | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | 108.1 FBC. | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | |
|