2007-11-16 16:06:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 8-10-07. ENERGY CALCULATIONS
 NEED TO BE ON FORM 600A-04R"R" , SEE 2004 FBC
 13-600.3.A. PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 8-10-07. WHEN RESUBMITTING
 THE ENERGY CALCULATIONS HAVE THEM SIGNED AND DATED BY
 THE PREPARER AND THE "OWNER/AGENT" , SEE 2004 FBC
 13-600.3.A.
  
 3) AS NOTED IN LAST REVIEW 8-10-07 NOTE #4. THE
 BATHROOM WILL REQUIRE AN 50 CFM EXHAUST FAN, SEE 2004
 FBC/R R303.3 EXCEP., SHOW ON ELECTRICAL AND MECHANICAL
 (A/C) PLANS.
  
 4) AS NOTED IN LAST REVIEW 8-10-07 NOTE #5. PLEASE
 SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS
 (MECHANICAL PLAN, ENERGY CALCULATIONS, AND COOLING LOAD
 CALCULATIONS), SEE 2004 FBC CITY WPB AMEND. 106.1.
  
 5)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;