Plan Review Notes For Permit 07080194 |
Permit Number |
07080194 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-10 13:49:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE | | 2004 FBC 13-600.3.A. PLEASE CORRECT. | | | | 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS HAVE THEM | | SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT, | | SEE 2004 FBC 13-600.3.A. | | | | 3) ENERGY CAL'S. STATE UNDUCTED A/C SYSTEMS TO BE | | INSTALLED, PLEASE SUBMIT MECHANICAL PLANS SHOWING ALL | | A/C EQUIPMENT AND A EQUIPMENT LISTING WITH ALL | | PERTINENT INFORMATION ON IT, SEE 2004 FBC CITY WPB | | AMEND. 106.3.5.4 (10). | | | | 4)THE BATHROOM WILL REQUIRE AN 50 CFM EXHAUST FAN, SEE | | 2004 FBC/R R303.3 EXCEP., PLEASE CORRECT. | | | | 5) PLEASE SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS, | | SEE 2004 FBC CITY WPB AMEND. 106.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL: [email protected]. |
|