2007-08-10 13:49:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 2004 FBC 13-600.3.A. PLEASE CORRECT.
  
 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS HAVE THEM
 SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT,
 SEE 2004 FBC 13-600.3.A.
  
 3) ENERGY CAL'S. STATE UNDUCTED A/C SYSTEMS TO BE
 INSTALLED, PLEASE SUBMIT MECHANICAL PLANS SHOWING ALL
 A/C EQUIPMENT AND A EQUIPMENT LISTING WITH ALL
 PERTINENT INFORMATION ON IT, SEE 2004 FBC CITY WPB
 AMEND. 106.3.5.4 (10).
  
 4)THE BATHROOM WILL REQUIRE AN 50 CFM EXHAUST FAN, SEE
 2004 FBC/R R303.3 EXCEP., PLEASE CORRECT.
  
 5) PLEASE SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS,
 SEE 2004 FBC CITY WPB AMEND. 106.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].