2007-08-09 15:29:59 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT |
| LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH |
| 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY |
| 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE |
| INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED |
| TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42. |
| |
| 2} 220.54 ELECTRIC CLOTHES DRYERS ? DWELLING UNIT(S) |
| THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A |
| DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS |
| (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS |
| LARGER, FOR EACH DRYER SERVED. |
| |
| 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| DEFICIENCIES. |
| |
| 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |