 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE
 INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED
 TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.
  
 2} 220.54 ELECTRIC CLOTHES DRYERS ? DWELLING UNIT(S)
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A
 DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS
 (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS
 LARGER, FOR EACH DRYER SERVED.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  