2007-08-29 18:00:56 | RESIDENTIAL ADDITION BUILDING FIRST REVIEW CHECKLIST. |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| 2004 WITH 2007 REVISIONS. |
| |
| 1-RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED |
| PRIOR TO ISSUING THE PERMIT AS REQ'D BY SEC. 713.13 |
| FLORIDA STATUTE. |
| |
| 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD. |
| (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| DUE. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW.PERMIT VALUATION WAS UPDATED TO $86,732 ACCORDING |
| TO THE ICC BUILDING VALUATION DATATABLE AS REQ'D BY |
| SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004. THEREFORE, |
| OWES 1,187.17 FOR BUILDING VALUATION AND RADON FEES. |
| |
| 4- PROVIDE SOIL TEST REPORT AS REQUIRED BY NOTES ON |
| FOUNDATION PLAN AND SEC.R401.4 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 5- SPECIFY CONSTRUCTION TYPE ON PLANS AS REQ'D BY SEC. |
| 602.1 FBC 2004. |
| |
| 6- IDENTIFYEXISTING ROOMS ADJACENT TO NEW ADDITION TO |
| CHECK IF EGRESS OPENINGS ARE NOT BLOCKED AND CHECK |
| COMPLIANCE WITH SEC. R310 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 7- PLANS ARE MISSING THE SOUTH EXTERIOR ELEVATION. |
| PROVIDE THIS ELEVATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 8-PROVIDE ALL DIMENSIONS IN THE NEW SURVEY, INCLUDING |
| THE BUILDING SETBACKS. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| ALSO,SURVEY NEEDS TO HAVE ORIGINAL SURVEYOR SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE. |
| |
| 9- ENERGY CALCULATIONS: |
| A) PROVIDE 2 COPIES. |
| B) PROVIDE REVISED FORM 600A-2004R. |
| C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| D) CLARIFY WHAT ARE ALL THE EXTERIOR AND ADJACENT |
| WALLS SHOWN ON ITEM #9. |
| E) PREPARER TO SIGN AND DATE FORM. |
| F) OWNER/AGENT TO SIGN AND DATE FORM. |
| G) OVERHANG HEIGHT IS INCORRECT. IT CAN'T BE 1. SEE |
| EXTERIOR ELEVATIONS AND REVISE AS REQUIRED. |
| H) REVISE BUILDING ORIENTATION. SEE PLANS AND SURVEY |
| FOR CORRECT BUILDING ORIENTATION AND REVISE AS REQ'D. |
| |
| 10- PROVIDE PRODUCT APPROVAL AS REQ'D BY DCA RULE 9B-72 |
| FOR: |
| A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVERPAGE AND PAGE WHERE CONNECTOR IS |
| SHOWN. |
| B) EXTERIOR DOOR. NOA 01-1218.05 SUBMITTED EXPIRED |
| ON 08/15/07. NEED TO PROVIDE CURRENT PRODUCT APPROVAL. |
| C) SINGLE HUNG WINDOW PRODUCT APPROVAL 05-0729.03 |
| SUBMITTED EXPIRED ON 07/11/07. PROVIDE CURRENT PRODUCT |
| APPROVAL. |
| D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| E) STORM SHUTTERS. AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE (SEE ATTACHED SAMPLE)AND KEY |
| PLAN.ALSO,CLEARLY MARK ON SHUTTERS DRAWINGS |
| SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, ETC.) |
| AND ANCHOR TYPE AND SPACING TO BE USED. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQ'D BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| ***NOTE: PLEASE MAKE SURE NAME OF ENGINEER IS ON |
| APPROVED AND REVIEWED STAMP. |
| |
| 12- SHEET A1: |
| A) REINFORCING STEEL SPECIFICATIONS SHOWN ON |
| FOUNDATION SCHEDULE DON'T MATCH SPECS SHOWN ON |
| FOUNDATION PLAN. REVISE AS REQUIRED TO MATCH. |
| B) SPECIFY ATTIC ACCESS LOCATION AND SIZE TO COMPLY |
| WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 13- TYPICAL WALL SECTION A/A-2: |
| A) SIZE OF FOOTING DOESN'T MATCH SIZE SHOWN ON |
| FOUNDATION PLAN. REVISE AS REQ'D. |
| B) REVISE SPECIFICATIONS FOR ROOF SHEATHINGNAILING |
| SPACING ON ZONE 3 AREAS. SEE SEC. R803.2.3.1 OF 2004 |
| FLORIDA RESIDENTIAL CODE AND REVISE AS REQ'D. |
| C) CLARIFY SPECS FOR INTERIOR FURRING STRIPS SIZE. |
| IS IT REALLY 2X4'S AT 24" O.C. WITH R11 INSULATION?. |
| THIS IS TYP. THE SPECS FOR A FRAMED BUILDING. REVISE |
| CLARIFY AS REQUIRED. |
| ALSO,COORDINATE INFORMATION WITH THEENERGY |
| CALCULATIONS. |
| D) SPECIFY FIREBLOCKING AS REQ'D BE SEC. R602.1.2 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| E0 CLARIFY/REVISE SPECS FOR STUCCO FINISH OVER METAL |
| HIGHRIB LATH.ARE THESE THE SPECS FOR THE SOFFIT. IF |
| SO, THEN SHOW ARROW POINTING TO CORRECT LOCATION. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |
| |
| |
| |
| |