Plan Review Notes For Permit 07080166 |
Permit Number |
07080166 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-10 13:06:36 | 1. SINCE THE BUILDING IS FIRE SPRINKLER PROTECTED, THE | | ROOM WHERE THE PROPOSED FM 200 SYSTEM IS BEING PLANNED | | MUST BE EQUIPPED WITH AUTOMATIC FIRE SPRINKLER HEADS | | CONNECTED TO THE MAIN BUILDING'S SYSTEM. THE SERVER | | ROOM WILL CONTAIN THE FM 200 SYSTEM AND THE REQUIRED | | FIRE SPRINKLER PROTECTION THAT IS REQUIRED PER NFPA | | 75. | | | | 2. THE PRORPOSED FM 200 SYSTEM SHALL BE INSTALLED IN AN | | APPROVED MANNER AND COMPLY WITH ALL OF THE TECHNICAL | | REQUIREMENTS OF NFPA 2001 AND ALL OTHER APPLICABLE | | CODES AND STANDARDS. | | | | 3. FLOOR PLAN NOTES INDICATES THAT "ALL DOORS SWING | | OUT" BY OTHERS. PLANS DISPLAY DOORS SWINGING IN. | | | | 4. THE FM 200 SYSTEM MUST BE INSPECTED, TESTED, AND | | APPROVED BY THIS OFFICE AS WELL AS THE MECHANICAL AND | | PLUBMING DEPARTMENTS PRIOR TO RECEIVING FINAL | | APPROVAL. | | | | 5. ALL WARNING DEVICES ILLUSTRATED ON THE PLANS SHALL | | PROVIDE THE WARNING MESSAGES OR SIGNALS AS INTENDED. | | | | 6. ALL WORK SUBJECT TO FIELD INSPECTION. | | | | 7. PLANS PROVIDES THE NECESSARY INSTALLATION AND | | TESTING INFORMATION FOR THE SYSTEM. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|