Plan Review Notes For Permit 07080166
Permit Number 07080166
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-10 13:06:361. SINCE THE BUILDING IS FIRE SPRINKLER PROTECTED, THE
 ROOM WHERE THE PROPOSED FM 200 SYSTEM IS BEING PLANNED
 MUST BE EQUIPPED WITH AUTOMATIC FIRE SPRINKLER HEADS
 CONNECTED TO THE MAIN BUILDING'S SYSTEM. THE SERVER
 ROOM WILL CONTAIN THE FM 200 SYSTEM AND THE REQUIRED
 FIRE SPRINKLER PROTECTION THAT IS REQUIRED PER NFPA
 75.
  
 2. THE PRORPOSED FM 200 SYSTEM SHALL BE INSTALLED IN AN
 APPROVED MANNER AND COMPLY WITH ALL OF THE TECHNICAL
 REQUIREMENTS OF NFPA 2001 AND ALL OTHER APPLICABLE
 CODES AND STANDARDS.
  
 3. FLOOR PLAN NOTES INDICATES THAT "ALL DOORS SWING
 OUT" BY OTHERS. PLANS DISPLAY DOORS SWINGING IN.
  
 4. THE FM 200 SYSTEM MUST BE INSPECTED, TESTED, AND
 APPROVED BY THIS OFFICE AS WELL AS THE MECHANICAL AND
 PLUBMING DEPARTMENTS PRIOR TO RECEIVING FINAL
 APPROVAL.
  
 5. ALL WARNING DEVICES ILLUSTRATED ON THE PLANS SHALL
 PROVIDE THE WARNING MESSAGES OR SIGNALS AS INTENDED.
  
 6. ALL WORK SUBJECT TO FIELD INSPECTION.
  
 7. PLANS PROVIDES THE NECESSARY INSTALLATION AND
 TESTING INFORMATION FOR THE SYSTEM.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX