Plan Review Notes For Permit 07080145 |
Permit Number |
07080145 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-07-17 15:47:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLANS AND COOLING LOAD CAL'S. | | | | *** DENIED *** | | | | 1) THE COOLING LOAD CALCULATIONS FOR ZONE #1 ARE | | CALLING FOR 33,029 TOTAL COOLING BTU'S, THE MECHANICAL | | PLAN EQUIPMENT SCHEDULE FOR SYSTEM #1 SHOWS 43,000 | | TOTAL COOLING BTU'S, THE PLANS CAN ONLY CALL FOR 15% | | MORE TOTAL COOLING BTU'S THAN THE COOLING LOAD | | CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1.1.A 3.5 TON | | SYSTEM IS TO LARGE, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|