2008-07-17 15:47:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS AND COOLING LOAD CAL'S.
  
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS FOR ZONE #1 ARE
 CALLING FOR 33,029 TOTAL COOLING BTU'S, THE MECHANICAL
 PLAN EQUIPMENT SCHEDULE FOR SYSTEM #1 SHOWS 43,000
 TOTAL COOLING BTU'S, THE PLANS CAN ONLY CALL FOR 15%
 MORE TOTAL COOLING BTU'S THAN THE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1.1.A 3.5 TON
 SYSTEM IS TO LARGE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]