2008-06-13 14:53:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN.
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS WILL NEED TO BE
 REVISED AS THE ZONES BEING SERVICED BY EACH UNIT HAVE
 CHANGED, PER 2004 FBC 13-607.1.ABC.1.
  
 2) THE FIRST FLOOR PLAN SHOWS A 12" DUCT COMING FROM
 THE SECOND FLOOR, BUT THE SECOND FLOOR PLAN SHOWS NO
 12" DUCT GOING TO THE FIRST FLOOR, PLEASE CORRECT.
  
 3) PLEASE LIST ALL A/C EQUIPMENT AS #1 OR #2 (AIR
 HANDLERS AND CONDENSERS).
  
 3) THE 14X14 RETURN AIR TRANSFER GRILL IS TO SMALL FOR
 THE RETURN AIR TO PASS THROUGH FROM THE FIRST FLOOR AND
 THE MASTER SUITE, SEE 2004 FBC/R M1602.4.
  
 **2004 FBC/R M1602.4 BALANCED RETURN AIR. TRANSFER
 GRILLES SHALL USE 50 SQUARE INCHES (OF GRILLE AREA) TO
 100 CFM (OF SUPPLY AIR) FOR SIZING THROUGH-THE-WALL
 TRANSFER GRILLES AND USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE
 (A)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]