Plan Review Notes
Plan Review Notes For Permit 07080145
Permit Number 07080145
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-28 16:30:41RESIDENTIAL ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-OWES $15.86 FOR NEW ADDITION RADON FEES. (REPEAT
 COMMENT).
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13FLORIDA STATUTE..
  
 3-SHEET 1 OF 6:
 A)THIS BUILDING IS NOT CONSTRUCTION TYPE 3.SEE
 SEC.602.1 FBC 2004FOR CONSTRUCTION TYPES AND REVISE
 AS REQUIRED.
  
 B) SPECIFY ALL LOADS AS REQUIRED BY TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE. MISSING THESLEEPING
 AND NON SLEEPING ROOMS AND STAIRS UNIFORM DISTRIBUTED
 LIVE LOADS. PROVIDE ALL THE REQUIRED INFORMATION FROM
 TABLE R301.5. (REPEAT COMMENT).
  
 C) THIS IS NOT JUST AN ALTERATION TYPE II, BUT AN
 ADDITION AS WELL. SEE CHAPTER 9 OF 2004 FLORIDA
 EXISTING BUILDING CODE. AND REVISE INFORMATION AS
 REQUIRED.
  
 4- SOIL TEST REPORT SUBMITTED:
 A) ENGINEERING FIRM NEEDS TO SHOWTHE FIRM'S
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) REVISE PROPOSED ADDITION SQUARE FOOTAGE.IT'S
 NOT 900 SF. SEE PLANS FOR CORRECT SQUARE FOOTAGE.
  
 5- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. THEREFORE NEED TO SPECIFY CEILING FAN SIZES TO
 VERIFY COMPLIANCE WITH TABLE 13-607.1.A.1 OF FBC 2004.
 (REPEAT COMMENT).SIZE OF CEILING PLANS SHOWN ON PLANS
 DON'T MEET THE MINIMUM SIZES SHOWN ON TABLE
 13-607.1.A.1 OF FBC 2004. AND, ENERGY CALCULATIONS ARE
 TAKEN FOR THE ENTIRE HOUSE. THEREFORE, NEED TO SPECIFY
 CEILING FAN SIZE ON EACH ROOM OF THE HOUSE. SEEABOVE
 TABLE FOR MIN.SIZE REQUIRED.
  
 6-SHEET 3 OF 6:SIZE OF FOOTING SPECIFIED IN
 FOUNDATION PLAN DOESN'T MATCHSIZE SHOWN ON TYPICAL
 FOOTING ATTACHMENT. REVISE AS REQUIRED. (REPEAT
 COMMENT).
  
 7-SHEET 4 OF 6:STAIRWAY BEARING WALL IS SHOWN
 INCORRECTLY ON 1ST FLOOR PLAN.PLAN SHOWS THE
 GUARDRAIL AND NOT THE WALL. (REPEAT COMMENT). REVISE AS
 REQUIRED.
  
 8- SHEET5 OF 6:
 A) REVISE RAILING HEIGHT SHOWN ON STAIRSECTION AND
 STAIR PLAN.SEE SEC. R311.5.6 OF 2004 FLORIDA
 RESIDENTIAL CODE. (REPEAT COMMENT).
  
 B) NUMBER OF RISERS SHOWN (14) ARE NOT ENOUGH.
 REVISENUMBER OF RISERS AS REQUIRED AND REVISE FLOOR
 PLANS AS REQUIRED ALSO.
  
 C) SPECIFY RISER HEIGHT IN INCHES.7.67" IS NOT A
 CORRECT DIMENSION. HOW DO YOU MEASURE IT?. PROVIDE
 CORRECT DIMENSION TO VERIFY COMPLIANCE WITH SEC.
 R311.5.3 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 D) 9" TREAD REQUIRES MINIMUM 1" NOSING.2X10 TREADS
 AS SPECIFIED ON DETAILS DON'T PROVIDE THE 1" NOSING.
 SEE SEC. R311.5.3.3 OF 2004 FLORIDA RESIDENTIAL CODE
 AND REVISE AS REQUIRED. COORDINATE WITHITEM 8(B) AND
 8(C) ABOVE. ALSO, PROVIDE SPECIFICATIONS FOR NOSING
 PROFILE TO COMPLY WITHTHIS CODE SECTION.
  
 9- SHEET 6 OF 6:
 A) COORDINATEALLSTRUCTURALCONNECTORS SPECIFIED
 ON WALL SECTIONS AND DETAILS WITH THOSE SPECIFIED ON
 TRUSS ANCHOR SCHEDULE AND ROOF/FLOORFRAMING PLANS.
 (REPEAT COMMENT).
  
 B) WALL SECTION B-B:SIMPSON LSTA24 STRAP SPECIFIED
 TOTRANSFER LOAD TO THE EXISTING CONCRETE BLOCK WALL
 IS TOO SHORT.ALSO, NEED TO SPECIFYA WOOD TO MASONRY
 CONNECTOR. OTHERWISE PROVIDE COMPLETE DETAIL AND
 ENGINEERINGSHOWING HOW PROPOSED STRAP WILL BE NAILED
 TO RESIST THE CALCULATED LOADS.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 CALCULATED LOADS OFSEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712