2007-08-23 16:20:22 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| LOCATIONS. |
| NOTE: NOT ALL WASTE AND TRAPS ARE SIZED ON SHEET 4, |
| SANITARY ISOMETRIC RISER DIAGRAM. PLEASE CORRECT THIS |
| ON THE RESUBMITTAL. |
| |
| 2. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DOES NOT |
| REFLECT THE FLOOR PLAN PER FBC-2004 CHAPTER 1, THE CITY |
| OF WEST PALM BEACH AMENDMENTS SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. PLEASE CORRECT THE FOLLOWING. |
| |
| A} THE RELOCATED DOUBLE BOWL KITCHEN SINK IS MISSING |
| FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM. |
| PLEASE CORRECT THIS AND RESUBMIT. |
| |
| B} THE RECONFIGURED EXISTING 1ST FLOOR BATH IS MISSING |
| FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM. |
| PLEASE CORRECT THIS AND RESUBMIT. |
| |
| C} THERE ARE TWO WASHING MACHINES INDICATED ON THE |
| SANITARY ISOMETRIC PLUMBING RISER DIAGRAM BUT ONLY ONE |
| (WASHING MACHINE) IS BEING INDICATED ON THE FLOOR PLAN. |
| PLEASE CLARIFY AND CORRECT THIS ON THE RESUBMITTAL. |
| |
| D} THE 2ND FLOOR MASTER BATH. |
| |
| 3. SHEET 4, SANITARY ISOMETRIC RISER DIAGRAM THE |
| RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF |
| THE WET VENTED BATHROOM PER FBC-2004, PLUMBING, SECTION |
| 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| NOTE: ALSO THE FOLLOWING IS REQUIRED FOR THE WASHING |
| MACHINE. |
| |
| (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. |
| |
| (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. PLEASE INDICATE THE WASHING MACHINE |
| STANDPIPE. |
| |
| (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM) |
| NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 |
| INCH. |
| |
| (D) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT |
| 4 FEET ABOVE FINNISH FLOOR (4' A.F.F.) |
| |
| 4. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| THE INDICATED PLUMBING TIED INTO THE 2ND FLOOR PLUMBING |
| STACK ON THE !ST FLOOR IS WRONG PER FBC-2004 PLUMBING, |
| SECTION 908.3 CONNECTION AT DIFFERENT |
| LEVELS. WHERE THE FIXTURE DRAINS CONNECT |
| AT DIFFERENT LEVELS, THE VENT SHALL |
| CONNECT AS A VERTICAL EXTENTION OF THE |
| VERTICLE DRAIN. THE VERTICAL DRAIN PIPE CONNECCTING THE |
| TWO FIXTURE DRAINS SHALL |
| BE CONSIDERED THE VENT FOR THE LOWER |
| FIXTURE DRAIN, AND SHALL BE SIZED IN |
| ACCORDANCE WITH TABLE 908.3. THE UPPER |
| FIXTURE SHALL NOT BE A WATER CLOSET. |
| |
| 5. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| A VENT IS REQUIRED FOR THE 2ND FLOORMASTER BATH |
| SHOWER AND TUB PER TABLE 906.1 BECAUSE THE 2 INCH TRAPS |
| ARE MORE THAN 6 FEET FROM THE VENT. |
| |
| 6. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| A TWO-WAY CLEANOUT IS REQUIRED PER FBC-2004 PLUMBING |
| SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE |
| JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE |
| INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM |
| WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED |
| SHEETS FOR REFERENCE ONLY. |
| |
| **NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR |
| REFERENCE FOR RESUBMITTAL AND PLEASE REFERENCE THE |
| SANITARY PLUMBING ISOMETRIC RISER DIAGRAM THAT REFLECTS |
| THE FLOOR PLAN AND IS CODE COMPLIANT ATTACHED TO THESE |
| COMMENTS FOR THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |