Plan Review Notes
Plan Review Notes For Permit 07080145
Permit Number 07080145
Review Stop P
Sequence Number 1
Notes
Date Text
2007-08-23 16:20:22DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL WASTE AND TRAPS ARE SIZED ON SHEET 4,
 SANITARY ISOMETRIC RISER DIAGRAM. PLEASE CORRECT THIS
 ON THE RESUBMITTAL.
  
 2. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DOES NOT
 REFLECT THE FLOOR PLAN PER FBC-2004 CHAPTER 1, THE CITY
 OF WEST PALM BEACH AMENDMENTS SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL. PLEASE CORRECT THE FOLLOWING.
  
 A} THE RELOCATED DOUBLE BOWL KITCHEN SINK IS MISSING
 FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM.
 PLEASE CORRECT THIS AND RESUBMIT.
  
 B} THE RECONFIGURED EXISTING 1ST FLOOR BATH IS MISSING
 FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM.
 PLEASE CORRECT THIS AND RESUBMIT.
  
 C} THERE ARE TWO WASHING MACHINES INDICATED ON THE
 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM BUT ONLY ONE
 (WASHING MACHINE) IS BEING INDICATED ON THE FLOOR PLAN.
 PLEASE CLARIFY AND CORRECT THIS ON THE RESUBMITTAL.
  
 D} THE 2ND FLOOR MASTER BATH.
  
 3. SHEET 4, SANITARY ISOMETRIC RISER DIAGRAM THE
 RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF
 THE WET VENTED BATHROOM PER FBC-2004, PLUMBING, SECTION
 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: ALSO THE FOLLOWING IS REQUIRED FOR THE WASHING
 MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE WASHING MACHINE
 STANDPIPE.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3
 INCH.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 4 FEET ABOVE FINNISH FLOOR (4' A.F.F.)
  
 4. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM
 THE INDICATED PLUMBING TIED INTO THE 2ND FLOOR PLUMBING
 STACK ON THE !ST FLOOR IS WRONG PER FBC-2004 PLUMBING,
 SECTION 908.3 CONNECTION AT DIFFERENT
 LEVELS. WHERE THE FIXTURE DRAINS CONNECT
 AT DIFFERENT LEVELS, THE VENT SHALL
 CONNECT AS A VERTICAL EXTENTION OF THE
 VERTICLE DRAIN. THE VERTICAL DRAIN PIPE CONNECCTING THE
 TWO FIXTURE DRAINS SHALL
 BE CONSIDERED THE VENT FOR THE LOWER
 FIXTURE DRAIN, AND SHALL BE SIZED IN
 ACCORDANCE WITH TABLE 908.3. THE UPPER
 FIXTURE SHALL NOT BE A WATER CLOSET.
  
 5. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM
 A VENT IS REQUIRED FOR THE 2ND FLOORMASTER BATH
 SHOWER AND TUB PER TABLE 906.1 BECAUSE THE 2 INCH TRAPS
 ARE MORE THAN 6 FEET FROM THE VENT.
  
 6. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM
 A TWO-WAY CLEANOUT IS REQUIRED PER FBC-2004 PLUMBING
 SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE
 INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM
 WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 **NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR RESUBMITTAL AND PLEASE REFERENCE THE
 SANITARY PLUMBING ISOMETRIC RISER DIAGRAM THAT REFLECTS
 THE FLOOR PLAN AND IS CODE COMPLIANT ATTACHED TO THESE
 COMMENTS FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER