Plan Review Notes
Plan Review Notes For Permit 07080145
Permit Number 07080145
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-13 16:00:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED THE INFORMATION OF THE
 PERSON RESPONSIBLE FOR THE DESIGN ON THEM (BOTH PAGES.
 PER FBC 104.2.1.
  
 2) SHOW ON MECHANICAL PLANS THE CFM'S FOR EACH OF THE
 BATHROOM EXHAUST FANS, SEE 2004 FBC/R R303.3 EXCEPTT.
  
 3) EXISTING BATHROOM #2 REQUIRES AN EXHAUST FAN, AS
 SHOWN ON ELECTRICAL PLAN, SEE 2004 FBC/R R303.3 EXCEP.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].