Plan Review Notes For Permit 07080145 |
Permit Number |
07080145 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-15 14:13:12 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | THE FOLLOWING: | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | DESIGNED. | | | | 2} INDICATE IF THE SERVICE SHOWN ON THE PLAN IS NEW OR | | EXISTING. | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | SIZE AND TYPE PER 106.3.5.4 FBC. | | | | 5} THE PANEL SCHEDULE LISTS TWO AIR HANDLERS, 1 @ 10000 | | AND 1@ 5500 WATTS. THE CALCULATION ONLY LISTS 10000 | | WATTS OF HEAT. PLEASE CORRELATE SAME. | | | | 6} THE SPA IN THE MASTER BATHROOM IS NOT LISTED IN THE | | SCHEDULE OR IN THE CALCS. ALSO IT MUST BE GFCI | | PROTECTED PER 680.43(A)(2). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | | | |
|