 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 2} INDICATE IF THE SERVICE SHOWN ON THE PLAN IS NEW OR
 EXISTING.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE PER 106.3.5.4 FBC.
  
 5} THE PANEL SCHEDULE LISTS TWO AIR HANDLERS, 1 @ 10000
 AND 1@ 5500 WATTS. THE CALCULATION ONLY LISTS 10000
 WATTS OF HEAT. PLEASE CORRELATE SAME.
  
 6} THE SPA IN THE MASTER BATHROOM IS NOT LISTED IN THE
 SCHEDULE OR IN THE CALCS. ALSO IT MUST BE GFCI
 PROTECTED PER 680.43(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER